Stulz CyberOne EC CW Installation, Operation And Maintenance Manual Download Page 16

CyberOne EC CW IOM Manual 

 

11 

 

 
 

 

Spot type water detector

 

Remove the protective cover and connect two control wires 

to the terminals on the base (terminal

 

lugs are provided). Replace the cover 
and place the water detector(s) on the 
floor with the metal electrodes facing 
down. When water is present, current 
will flow between the electrodes. The 
base is provided with a mounting hole 
in the center which may be used to 
secure the water detector in place.

 

NOTE

 

Do not place the spot type water detector on an 
electrically conductive surface.

 

Cable type water detector

 

Lay the cable water detector flat across the sub-floor where 
water could collect. When

 

water  is  present,  current  will 
flow between the two wires. A 
two conductor wire harness is 
provided with a quick connect

 

fitting on the end. The harness mates to the fitting on the 
water detector cable and connects it to the terminal block 
inside the electric box.

 

2.6.5

 

Plenum Box Assembly

 

If an optional plenum box (plenum extension box or 1-, 2- or 
3-way discharge plenum box) is purchased it is typically 
shipped loose. To install a plenum box, first apply a strip of 
sealing foam around the top flange of the A/C unit or, run a 
bead of silicone sealant. Place the plenum assembly on top 
of  the  unit  as  shown  in  Figure  5 on page  9.  Attach  the 
plenum with the self-tapping screws provided. Holes are 

pre-drilled in the unit and the plenum box. If mounting an air 
distribution plenum box, the grilles may be removed for access 
to the mounting holes.

 

 

2.7

 

Piping Connections  

For downflow models, piping is routed through the bottom of 
the cabinet. For upflow models, the piping is routed through

 

the top of the cabinet. If an optional plenum box is installed, 
drill holes in the top or in the side of the box, as preferred, to 
route the piping out.

 

2.7.1

 

Condensate Drain

 

2.7.1.1

 

Gravity Drain

 

A 7/8 inch O.D. copper (sweat type) line is provided to drain 

the condensate pan. An S-trap is internally-installed in the 
condensate drain piping. An installer should connect a 7/8 
inch I.D. drain line to remove water from the cabinet. If an 
optional humidifier is used, the drain line from the humidifier 
is typically connected to the condensate drain line.

 

NOTE

 

During normal operation, the humidifier drain line 
discharges (hot) water into the condensate drain 
line.

 

The drain line must be located so it will not be exposed to 
freezing temperatures. The diameter of the drain line should 
be the full size of the connection.

 

NOTE

 

Pour some water into the condensate drain pan(s) 
prior to start-up. This fills the trap and prevents air 
from being drawn up the drain lines.

 

2.7.1.2

 

Condensate Pump

 

An optional condensate pump is normally factory installed. 
The drain connection line is typically 1/2” I.D. vinyl tubing or 
a 1/2” O.D. copper (sweat connection) may be used.

 

 

Figure 7. 

Condensate Pump

 

 
 
 
 
 
 
 

 

 
 

INLET 7/8 OD

 

 

OUTLET 1/2 OD

 

Summary of Contents for CyberOne EC CW

Page 1: ...CyberOne EC CW Installation Operation and Maintenance Manual Perimeter Precision Air Handlers 12 kW 35 kW 60 Hz...

Page 2: ...r Technology Systems Inc STULZ This document contains con dential and proprietary information of STULZ Distributing or photocopying this document for external distribution is in direct violation of U...

Page 3: ...erns 8 2 6 Optional Equipment Field Installed 10 2 6 1 Floor Stand 10 2 6 2 Remote Controller Terminal 10 2 6 3 Remote Temperature Humidity Sensor 10 2 6 4 Remote Water Detector 10 2 6 5 Plenum Box As...

Page 4: ...1 Typical CW Internal Layout Down ow Con guration 3 Figure 2 Typical CW Internal Layout Up ow Con guration 3 Figure 3 Recommended Installation Clearance 6 Figure 4 Down ow Con guration TypicalAir Pat...

Page 5: ...an Cooling COS CyberOne 042 060 096 120 CW Chilled Water D Downflow Air U Upflow Air EC Direct Driven single inlet two fold backward curved radial fan with electronically commutated EC motor Call Prod...

Page 6: ...understandallrelevant instructions recommendations and guidelines contained within this manual Certain maintenance orcleaning procedures maycallforthe useandhandlingofchemicals solvents orcleansers Al...

Page 7: ...nting to a wall or controlpanel An operating manual for the system controller is provided under separate cover Refer to that manual for detailed instructions on operating the system controller provide...

Page 8: ...CH NOTE 1 HOT WATER REHEAT COIL CONDENSATE PUMP FRONT SIDE RIGHT SIDE NOTES 1 SERVICE DISCONNECT SWITCH HANDLE IS MOUNTED TO FRONT DOOR OF CABINET 2 CABINET DOOR AND RIGHT SIDE ACCESS PANEL REMOVED TO...

Page 9: ...motor2 1 Upon correction of these failure conditions the motor will automatically reset 2 Upon correction of these failure conditions the motormust be manuallyreset byturning offpower for 20 seconds...

Page 10: ...Humidity T H Sensor A T H sensor may be selected as an option for use with the COS EC CW unit The sensor will be shipped loose for eld installation somewhere in the conditioned space away from the un...

Page 11: ...ner unless specified otherwise by the customer A plenum box if applicable is shipped separately Unpack and storethese itemsin asafe place unless you are using them immediately 2 2 Moving the Equipment...

Page 12: ...y air to only one room They have a compact footprint which allows the units to be placed in a corner or between cabinetry It is recommended to position the unit to obtain optimum aircirculation NOTE T...

Page 13: ...with the unit Ductwork may be connected with either pop rivets or self tapping screws 2 5 2 Up ow Con guration Air Patterns In a con gured unit the conditioned supply air has two methods of discharge...

Page 14: ...ns REAR DUCTED RETURN FRONT FREE RETURN RETURN AIR INLET RETURN AIR INLET SUPPLY AIR OUTLET TOP DUCTED DISCHARGE SUPPLY AIR OUTLET REAR DUCTED RETURN FRONT FREE RETURN RETURN AIR INLET RETURN AIR INLE...

Page 15: ...Temperature Humidity Sensor The remote temperature humidity T H sensor must be located so that it will properly sense the temperature humidity conditions to be controlled The T H sensor should not be...

Page 16: ...ws provided Holes are pre drilled in the unit and the plenum box If mounting an air distributionplenumbox the grillesmaybe removedforaccess to the mounting holes 2 7 Piping Connections Fordown owmodel...

Page 17: ...g supplied with the unit for all power and control eld wiring It is important to identify the optionsthat were purchased withthe unit in orderto con rm which eld connections arerequired NOTE If the na...

Page 18: ...orrequiresashielded cablewiththeshieldterminatedattheunitelectricbox Three control conductors are required Both the electric box and the sensorinclude aterminal stripwith box type lugsforwire connecti...

Page 19: ...rol valve and the temperature of the water has decreased as it passes through the unit 6 If a humidi er is present test humidi cation operation by creating a demand for humidi cation Use an amp metert...

Page 20: ...ked at least monthly and replaced as required NOTE Airqualityinconditionedspacesvaries Aschedule for checking air lters should be based on those conditions 4 2 2 EC Fan Periodically check the EC fan s...

Page 21: ...bable Cause Recommendation Chilled Water Valve Fails to Open or Close Temperature setpoint too high or low Adjust to correct temperature setting No control power to the chilled water valve Valve actua...

Page 22: ...heck filters and dampers Clear coil fins of debris Electric Heater Inoperable Circuit breaker tripped Check for short circuit reset circuit breaker Temperature setpoint too low Increase temperature se...

Page 23: ...ighten electrical connections Humidifier circuit breaker tripped Check for excess current draw by the humidifier electrodes Drain water from tank and refill Reset circuit breaker Defective contactor R...

Page 24: ...that uses the controller such as via BMS orthe controller terminal 2 Turnoffthewatersupplytothehumidi erusingthesmall manual ball valve in the unit skid under the compart ment where the humidi er is...

Page 25: ...e for the shipping charges If you do not have established credit with STULZ you must provide a freight carrier account number A written or faxed purchase order is required on warranty parts and must b...

Page 26: ...pan safety switch operates freely Additional Check chilled water hot water circuits for air bleed as required Coils clean and clear of obstructions Humidifier cylinder and controls operate properly Ta...

Page 27: ...l support call 888 529 1266 or email stulztechnicalsupport stulz ats com Support is available 24 7 365 Provide the model number serial number and STULZ item number from the unit nameplate This will sp...

Page 28: ...FPA National Fire Protection Agency CFM Cubic Feet Per Minute PH Phase EC Electronically Commutated PSI Pounds Per Square Inch DP Dewpoint PSIG Pounds Per Square Inch Gauge DX Direct Expansion RLA Run...

Page 29: ...ogy Systems Inc 1572 Tilco Drive Frederick MD 21704 301 620 2033 Fax 301 662 5487 info stulz ats com Technical Support 888 529 1266 www stulz usa com OCCO209A Feb 2020 STULZ Air Technology Systems Inc...

Reviews: