![Stulz CyberHandler 2 Installation, Operation And Maintenance Manual Download Page 9](http://html1.mh-extra.com/html/stulz/cyberhandler-2/cyberhandler-2_installation-operation-and-maintenance-manual_1387331009.webp)
CYBERHANDLER 2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
EN/05.2019 © STULZ GmbH – all rights reserved
9
4 Description
4 1
Type Code
The type code represents the unit variant of your air handling unit and can be found on the type
plate.
CH2 -
S1 -
ADB -
SH/RH
Product range
CyberHandler2
Size
From S1 to S9
Cooling Configuration
ADB:
Adiabatic only
CWT:
Chilled Water Top-Up Coil
CWR:
Chilled Water Redundant Coil
DXT:
DX Top-Up integrated system
DXR:
DX Redundant system with outdoor condensing unit
Installation Configurations
SH/RH:
Supply Horizontal/Return Horizontal (Wall)
SB/RH:
Supply Bottom/Return Horizontal (Roof)
SB/RB:
Supply Bottom/Return Bottom (Roof)
STULZ TECNIVEL SL
C/ Carabaña S/N -
28925 - Alcorcón
-Madrid - SPAIN
Tel: +34 915 571 130
E-mail: [email protected]
Product
Model
Seria No.
Supply voltage
Cooling capacity
Refrigerant
Max. operation pressure
Made in Spain
Year of manufacture
Weight
Max. Current
Contains fluorinated greenhouse
gases
Air Handling Unit
CH2-S1-ADB-SH/RH
CL-000-18
400 V ± 10 %
50 Hz ± 1 %
2018
276 A
252 Kw
R410A
40 Kg
83,5 T
42
bar
25
bar
BP
HP
CO2eq
Charge
Type
5325 Kg