CYBERHANDLER 2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
EN/05.2019 © STULZ GmbH – all rights reserved
13
Service doors must always be closed during transport
When delivery is accepted, the unit is to be checked against the delivery note for
completeness and checked for external damage which is to be recorded on the con-
signment note in the presence of the freight forwarder.
•
You receive the consignment papers with the delivery of the AHU.
•
The shipment is made ex works, in case of shipment damages, please assert your
claim directly towards the carrier.
5 Delivery/Transport/Storage
5 1
Delivery of units
5 2 Storage
5 3 Transport
The CyberHandler 2 unit is delivered either completely assembled or in separated unit compo-
nents divided as indicated in the unit drawing.
The complete units and individual modules must always be transported upright.
If you put the unit into intermediate storage before the installation, the following measures have
to be carried out to protect the unit from damage and corrosion:
• Make sure that the water connections are provided with protective hoods. If the intermediate
storage exceeds 2 months, we recommend filling the pipes with nitrogen.
• the temperature at the storage point should be within the range -10ºC to 50°C, and the site
should be dry and not exposed to direct sunlight.
• the unit should be stored packaged to avoid the risk of corrosion especially of the heat
exchanger fins.
5 3 1
Transport with forklift
When transporting the unit with a forklift truck, make sure that only the base frame or supplied
pallet rest on the forks and not the unit base.