STUDER INNOTEC

 

Users’ and Installers’ Handbook 

HPSI V2.0 E 

 page5 

Activate the minimum charge you wish to detect. 
Turn the screw slowly anti-clockwise 

 until 

the inverter activates. (green LED illuminated). 
 
Check that the inverter goes back to standby 
mode a couple of seconds after deactivation of 
all charges. 
 

 Warning 

: In maximum anti-clockwise position 

the inverter continues to work even if there is no 
load

Control 

The tension of the batteries is submitted to 
control. During their use, the tension must be 
between the following ranges : 
 
11.4 V and 16 V in the 12 Volt models, 
22.8 V and 32 V in the 24 Volt models, 
45.6 V and 61 V in the 48 Volt models.  
 
Outside these ranges the inverter is 
automatically disconnected. 
 
These values correspond to a no load situation 
and they are automatically adjusted according to 
the current of the battery. 
 
The internal temperature and the maximum 
power are also submitted to control. 
 
In the case of prolonged overload or deficient 
ventilation it is not possible to restart the inverter 
until it has cooled down. 

Indicators 

Green Run - LED (3) 

Illuminated: the inverter is connected. A 230 V 
tension is present in the outlet. 
Blinking : (only SI version) The inverter is in 
“ Autom. ” mode and no voltage is detected by 
the standby system. 
 

 A 230 V tension is intermittently present! 

Red Fault - LED (2) 

The inverter is stopped : 
The tension of the battery is not correct 
After an overload, overheating or short circuit 
To restart the inverter after a failure, put the 
switch (4) in “ OFF ” position for 10 seconds, 
then connect again

Safety 

The inverter is internally protected against 
overloads and short circuits. Should this 
protection fail, the inverter is equipped with a 
fuse (fire protection). If the fuse is broken, 
qualified technicians should control the 
installation and change the fuse. 

Internal fuse 

 

 

Fuse 

 Inverter HPSI  (CF8 fuse links) 

300 A 

2212 – 4424 

250A 5048 

 

The use of higher fuse value will not improve the 
performance of the inverter and will degrade 
safety protection ! 

Alarm contact 

A contact with no potential (0,5A - 60V) is 
available (12). It warns the user (alarm or control 
system) when the inverter has been stopped 
due to a failure or is out of use. It is off when the 
inverter is working.  

Maintenance  

The SI inverters do not need any special 
maintenance. The casing may be cleaned with a 
damp cloth (not wet). 
 
In the case of malfunction, the inverter should 
be sent to the salesperson for control. 

Legislation 

In all cases the assembly and installation must 
be done by qualified technicians, observing the 
national requirements and rules stipulated. You 
will find complete information about this in the 
relevant institutions. 

Limitation of liability 

STUDER INNOTEC cannot control  the 
installation, use and maintenance of the inverter. 
Thus, we are not responsible for damages, 
costs or losses resulting from an installation 
which is not in accordance with the regulations 
or inappropriate use or maintenance. 
 
The customer is always responsible for the use 
of the inverters STUDER INNOTEC. 
 
This device has not been designed and is not 
warranted for use in life support apparatus or 

Summary of Contents for HPSI 2212

Page 1: ...2 at Pnom Dynamic behaviour Normalization 0 5 ms for 0 to 100 load Frequency 50 Hz 0 01 Crystal control Charge detection User adjustable 0 5 to 20 W Maximum power load 15 min 1 3 1 6 x Pnom 25 C Maximum power load 3 min 1 6 2 x Pnom 25 C Peak power 5 sec 3 5 x Pnom Asymmetric charge Up to 2 x Pnom Cos φ max at Pnom 0 6 1 IP protection index IP 20 Forced ventilation From 45 C 3 C Overheating protec...

Page 2: ...tallers Handbook HPSI V2 0 E page1 Sinewave inverter HPSI series User s and Installer s Handbook STUDER INNOTEC Rue des Casernes 57 CH 1950 Sion Tel 41 0 27 205 60 80 Fax 41 0 27 205 60 88 info studer inno com www studer inno com ...

Page 3: ... 4 CONNECTION 4 USE 4 REMOTE CONTROL 4 Standby Level 1 4 Adjustment procedure 4 CONTROL 5 INDICATORS 5 Green Run LED 3 5 Red Fault LED 2 5 SAFETY 5 INTERNAL FUSE 5 ALARM CONTACT 5 MAINTENANCE 5 LEGISLATION 5 LIMITATION OF LIABILITY 5 DECLARATION OF CONFORMITY 7 EQUIVALENT CIRCUIT FOR HPSI INVERTER 8 DESCRIPTION AND WIRING DIAGRAM 9 TECHNICAL SPECIFICATIONS 10 ...

Page 4: ...c network generator may be connected to the output of the inverter because this could result in its destruction As for the usage of batteries follow the manufacturer s instructions Important After disconnecting the battery the output tension 230V may still remain for 30 seconds The ventilation of the device should never be obstructed Should the device be installed in an enclosed structure make sur...

Page 5: ...ected the LED blinks after some seconds which indicates that the standby mode has started If a user device is plugged in the green LED remains illuminated indicating the uninterrupted presence of 230V in the outlet If you wish to deactivate the standby mode put the switch in Lock position The inverter will be then working continuously Warning With the lock mode the no load consumption of the inver...

Page 6: ...inverter after a failure put the switch 4 in OFF position for 10 seconds then connect again Safety The inverter is internally protected against overloads and short circuits Should this protection fail the inverter is equipped with a fuse fire protection If the fuse is broken qualified technicians should control the installation and change the fuse Internal fuse Fuse Inverter HPSI CF8 fuse links 30...

Page 7: ...s with potential risks of serious harm to people or to the environment We do not accept any responsibility for any violation of patent rights or other third person rights resulting from the use of the inverter STUDER INNOTEC reserves the right to modify their products without previous notice ...

Page 8: ...57 CH 1950 Sion Declares that the product Sinewave inverter Product Name HPSI Series Model Number HPSI 2212 HPSI 4424 HPSI 5048 Are conform to the following product specifications EN 50081 I II EN 55014 EN 55022 EN 50091 2 EN 60950 IEC 801 II III IV CEI 555 LVD 73 23 EEC EMC Dir 89 336 EEC Full name position Date Signature Roland Studer General director 16 02 2000 ...

Page 9: ...blue wire and the yellow green wire This point can also be tied to ground if there is an existing ground Every ground point of appliances or plug should be tied together One side or the other of plus or minus battery input could also be tied to ground if needed A real neutral is an absolute need if there is a FI ground fault detector used as safety device In any case he installation of an inverter...

Page 10: ...Inverter stop when contact is closed Main switch Run indicator Green LED Fault indicator red LED Standby level adjustment Not avalable with Twinpower option Battery connection Minus battery Alarm contact 60V 0 5A potential free 9 2 3 Check battery polarity Battery size sould be ajusted to the inverters power Cbatt Ah 5 x Pnom Unom This value could be divided by two for short time applications 6 ...

Page 11: ...trol Charge detection User adjustable 0 3 to 20 W Maximum power charge 15 min 1 3n 1 6 x Pnom 25 C Maximum power charge 3 min 1 6 à 2 x Pnom 25 C Peak power 5 sec 3 5 x Pnom Asymmetric charge Up to 2 x Pnom Cos ϕ max at Pnom 0 6 1 IP protection index IP 20 Forced ventilation From 45 C to 3 C Overheating protection temperature 75 C 3 C Required battery capacity 5x Pnom Unom recommended value Acoust...

Reviews: