6.4.4
Activate the end of charge synchronization {6042}
This parameter activates the function of synchronization at 100 % of SOC under certain conditions
of end of charge.
For the synchronization to occur:
the voltage shall be above parameter {6024}
the current shall be below parameter {6025}
and this during a period defined by the parameter {6065}
This function is not compulsory because the BSP adjusts automatically the state of charge as per
the voltage.
6.4.5
End of charge voltage level {6024}
See explanation at parameter {6042}.
6.4.6
End of charge current level {6025}
See explanation at parameter {6042}.
6.4.7
Minimum time before end of charge {6065}
Minimum time in minutes before the end of charge can occur. See explanation at parameter
{6042}.
6.4.8
Temperature correction of the end of charge voltage {6048}
The voltage set with parameter {6024} can be corrected with this coefficient. By using a reference
temperature of 25 °C it is possible to have a similar charge behaviour of the Xtender, the
VarioTrack or the VarioString.
6.4.9
Activate the state of charge correction by the open circuit voltage
{6044}
When this parameter is activated, the state of charge is corrected by the battery voltage. This
function is only effective for lead-acid batteries.
6.4.10
Battery current limitation activated {6058}
6.4.11
Max battery charge current {6059}
The activation of the parameter {6058} allows to implement a global limit on the battery charge
current equal to the value of the parameter {6059} given the current measured by the BSP. This
limitation is imposed on VarioTracks and VarioStrings with software versions equal or greater than
1.5.30 and 1.5.20, respectively. Nonetheless, the limit does not affect the charge current of the
Xtenders.
6.4.12
Self-discharge rate {6019}
A battery gets discharged over time even when no current is consumed. This parameter allows to