Stuart Turner monsoon extra Installation Instructions Manual Download Page 18

- 18 -

Dry Run Protection

This pump is fitted with a safety control circuit, which will detect the following fault

condition:

Dry running caused by water starvation to the pump.

Should the pump run out of water it will stop as part of a “protective logic sequence”,

detailed below.

The fault should be rectified before re-starting the pump.  Check that there is sufficient

water supply to the pump and also ensure that all terminal fitting outlets are closed.

Protective Logic Sequence

If water starvation occurs and the power supply to the pump remains uninterrupted, the

pump controller will perform the following protective sequence.
1.

If the pump detects water starvation, it will stop operation after a 1 minute period.

2.

The pump will remain in the off condition for a period of 5 minutes.

3.

The pump will then re-start and if the water starvation condition remains present, the 
pump will then stop operation after a 1 minute period.

4.

The pump will remain in the off condition for a period of 5 minutes.

5.

The pump will then re-start and if the water starvation condition remains present, the 
pump will then stop operation after a 1 minute period.

6.

The pump will remain in the off condition for a period of 5 minutes.

7.

The pump will then re-start and if the water starvation condition remains present, the 
pump will then stop operation after a 1 minute period.

8.

After three consecutive resets are performed the pump will remain in the off 
condition indefinitely.

9.

To restart the pump, the power supply should be first isolated for a period of at least 
10 seconds before switching on again.

If the pump fails to operate normally after three attempts to re-start, then please consult

Stuart Turner on 01491 572655.

Flow Switch Circuit Test

1.

First confirm visually that the flow switch reed clamp has not been dislodged during 
handling or installation.  The clamp must be fully located within its flow switch 
body groove as shown.

2.

To carry out the following test you will need to obtain a magnet, a typical fridge 
magnet is suitable.

3.

Ensure the power supply is switched on.

4.

Position the magnet directly in front of the reed clamp as shown.  If pump does not 
start, then slowly move the magnet up and down to a position that exceeds the extent
of the reed clamp.  The pump should instantaneously start at some point during this 
extent of movement.  If this does not happen, this indicates a possible fault with the 
reed switch or the P.C.B which is located within the terminal box.  These should be 
checked electrically.  Consult Stuart Turner for further instructions.

Summary of Contents for monsoon extra

Page 1: ...onsoon Extra range is designed for pressure boosting applications in vented stored hot or cold clean water systems where under gravity no flow is available Inlet pressures to the pump and ambient temp...

Page 2: ...from pressure vessel thread Ensure that the fibre washer is present at the bottom of the fitting point Screw the pressure vessel clockwise until hand tight to achieve a water tight connection This dia...

Page 3: ...upwards Typical pump locations are in an airing cupboard or inside a vanity unit with a small purpose built dry and ventilated enclosure The enclosure should have a minimum clearance of 80 mm 3 betwee...

Page 4: ...ust also be within the maximum requirement of 8 metres for N1 3 and 13 metres for other models Hot Water Installations The preferred pump location is at floor level next to the hot water cylinder or a...

Page 5: ...The pump must be free to vent to the supply tanks at all times Hot Water Installations If it is not possible to locate the pump in the preferred area due to site limitations and it is necessary to pos...

Page 6: ...0 The pipework feeds to the storage tank should be of adequate size to ensure replenishment rate of tanks is sufficient to meet the needs of the pump Care should be taken in the design of pipework run...

Page 7: ...mm pipework Most preferred Fig 7 Least preferred N O T R E C C N O T R E C C 45 Pipework Connections Connection between pump and system outlets This should run as far as possible in 22 mm copper tube...

Page 8: ...ipe must be supported against collapse with the pipe manufacturers recommended support sleeve pipe insert c Appropriate plumbing fittings from the John Guest speedfit push in plumbing fitting range Ot...

Page 9: ...o pump head and that hoses are kept as straight as possible Do not kink or twist the hose In the case of horizontal feeds use a 22 mm John Guest stem elbow not supplied Do not bend the hose more than...

Page 10: ...connected to the fixed wiring of the mains supply Means for disconnection must be incorporated in the fixed wiring in accordance with the wiring rules A suitable method of connection would be via a d...

Page 11: ...The wire which is coloured brown must be connected to the terminal which is marked with the letter L or coloured red Wiring Diagrams The supply cord and internal wiring within the terminal box are ro...

Page 12: ...re fitted with a supply cord to the following specification Monsoon Extra N1 3 bar HO5VV F3 G 0 75 mm 6 Amp rated cable Monsoon Extra N2 4 N2 9 N3 7 bar HO7RN F3 G 1 0 mm 10 Amp rated cable If the sup...

Page 13: ...torage capacity is adequate to meet the demand Ensure the pump chamber is full of water before starting the pump Failure to do this could result in seal damage To ensure dry running does not occur the...

Page 14: ...unlikely event of a water leak any spillage is contained or routed to avoid electrics or areas sensitive to water damage 1 No routine maintenance is required but provision should be made for easy acce...

Page 15: ...for instructions on re starting pump 6 As water is heated scale deposits are released in areas of hard water usually south of a line between the Wash and Bristol Channel scale can cause the mechanica...

Page 16: ...20 kPa 4 2 bar 40 C 65 C 4 C 1 l min approx 140 kPa 1 4 bar 89 kPa 0 89 bar 1 metre 10 metres 47 metres 600 kPa 6 0 bar 40 C 65 C 4 C 1 l min approx 140 kPa 1 4 bar 89 kPa 0 89 bar Dimensions Length m...

Page 17: ...er Check tank volume is adequate Consult makers instructions Pump starts when outlets are off or Pump cycles hunts on off frequently Leak in system Low pre charge pressure in pressure vessel Debris un...

Page 18: ...ondition for a period of 5 minutes 7 The pump will then re start and if the water starvation condition remains present the pump will then stop operation after a 1 minute period 8 After three consecuti...

Page 19: ...ition Abide by the Water Supply Water Fittings Regulations 1999 Always install isolating valves to both suction and delivery pipe work Ensure earth continuity between suction and delivery pipes Always...

Page 20: ...1 572655 or return pump with accessories removed pipes etc Proof of purchase should accompany the returned unit to avoid delay in action Stuart Turner Ltd Henley on Thames Oxfordshire RG9 2AD ENGLAND...

Reviews: