16" Max.
LB-25 Shown
2,500 lb.
Max. load
Vent
FLOW
FLOW
450 lb. Max
Load
LB-25 Shown without riser
FLOW
FLOW
ON-THE-FLOOR DETAIL
(LB-125 SHOWN)
FLOW
FLOW
2,500 lb.
Max Load
Riser (sold separately)
Rebar
LB-25 Shown with riser
INTERIOR BELOW GRADE INSTALLATION INSTRUCTIONS
(LB-15, LB-25)
INTERIOR ABOVE GRADE INSTALLATION INSTRUCTIONS
(LB-15, LB-25, LB-35, LB-50, LB-125, LB-275)
If concrete slab falls within body of unit, reinforce with rebar,
extending 6" beyond footprint of unit to connect main floor slab.
When the jobsite requires burying unit flush with floor
without using a riser kit, maximum cover/unit top load rating is 450 lbs.
Native soil
CONNECTIONS
Install unit(s) as close as possible to fixtures/drains being serviced.
1.
Connect waste piping to the unit.
2.
Crushed aggregate or sand backfill
Concrete
EXCAVATION
Install unit(s) as close as possible to fixtures being serviced.
1.
Width and length of excavation shall be minimum 6" greater
2.
than the tank on all sides.
Depth of excavation shall be 6" deeper than tank bottom.
3.
Set the tank in well-packed crushed aggregate material
4.
approximately 3/4" size rock, or sand, with no fines.
CONNECTIONS
Connect waste piping to the unit.
1.
BACKFILLING & FINISHED CONCRETE SLAB
Before backfilling and pouring of slab secure cover(s) to the unit(s).
1.
Backfill using crushed aggregate material approximately 3/4" size rock or sand
2.
with no fines.
3. Place 6" aggregate base under slab.
3.
LAB BASIN SERIES INSTALLATION,
OPERATION AND MAINTENANCE GUIDE
ECO:
10/22/18
MJ
REV:
DATE:
DWG BY:
DESCRIPTION:
PROPRIETARY AND CONFIDENTIAL
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
STRIEM, LLC.
ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF
STRIEM, LLC.
IS
PROHIBITED.
NOTES:
Striem Lab Basins are not to be installed in any other manner except as shown. Consult local
codes for separate trapping requirements, cleanout locations and additional installation instructions.
Vent required on outlet pipe only if outlet diptube is present.