background image

Striem

3100 Brinkerhoff

Kansas City, KS 66115

Tel: 913-222-1500

Fax: 913-291-0457

www.

striemco.com

Made in the U.S.A

Adapter

Adapter

Cover

Cover

Gasket

Gasket

LB-275

(standard)

Upper clamp
Lower clamp

Lower clamp

Upper clamp

Cut location "C"

LR24 

(long riser)

(optional component)

Gasket

Upper Clamp

Lower Clamp

Cut location "B"

SR24 

(short riser)

(optional component)

Gasket

Lower Clamp

Upper Clamp

LB-35, LB-50, 

LB-125 & LB-275

(standard)

Adapter

Cover

Gasket

Upper clamp

Lower clamp

Figure 2

Adapter

Riser

Riser  

Distance from step 5

4"

Cut

Mark

Figure 3

Adapter

Riser

exceed 4"*

Must be at least

2-1/2" and cannot

Gasket

Unit

Riser/Adapter

Upper Clamp

Lower Clamp

Figure 4

*3" for a LB-35 with 4" connections

5.  Adjust 

adapter

 upwards to reach 20" to 22" 

6.  Adjust 

adapter

 upwards to reach 35" to 37"   

Cut location "A"

Adapter

Cover

Adapter & Cover 

(standard component)

FLOW

Finished floor

Figure 1

Riser Height

Adapter

Unit

Tools included (with base grease interceptor unit(s))

7/16" Nut driver tool/bit

Silver permanent marker

Tools Needed:

Tape measure

Regular or cordless drill with 1/2" chuck

Tools needed if Riser(s) require cutting:

Jigsaw or

Cordless circular saw or

Reciprocating saw

Riser Assembly Instructions/Steps:

If the unit is to be installed on grade (on-the-floor), there is no need for any adjustments.  

1.

The unit is ready to be put into service.

   

2.    If the unit is to be buried:  Once the unit is set so that the pipe connections line up with 

the jobsite piping, measure the total riser height needed from the top of the cover to finished 

grade.  Make sure you include any future tile work, etc. that may be installed 

in your finished grade measurements.  See figure 1. 

    

3.   Select the according riser(s) needed based off Table 1.

   

4.    If riser(s) are needed, remove the cover(s) from the adapter and remove the adapter from the 

main unit by loosening the upper clamp with the included nut driver bit (lower band is factory

set, do not adjust or remove).  On the floor near the unit, insert the adapter into the first riser 

until it stops.  If needed, insert the bottom of the first riser into the top of the second riser until  

it stops. You may need to tighten the upper clamps during this step to keep the risers from  

shifting. Adapter and riser(s) should sit level with each other.  Removal of the cover during this 

process will ease assembly.

   

5.    From the top of the adapter, measure your needed total riser height downward to the 

sidewall of the riser.  Then, add 

5”

 (for LB-35 or LB-50) or 

6”

 ( for LB-125, or LB-275).  

For example, if you have a LB-275 and need a 15-1/2” extension, you would measure 

down from the top of the adapter 21-1/2” (15-1/2” + 6” = 21-1/2”).  See Figure 2.

   

6.   Refer to Table 2, Table 3 or Table 3a to determine if, and where, any cuts need to be made.  

If a cut needs to be made, make a circular line around the sidewall of the riser with the 

included silver marker at your riser height 

+dimension from step 5

.  Using a jigsaw, circular 

saw or reciprocating saw, cut along your line.  Discard/recycle the cutoff scrap.

   

7.   Whether the riser needs to be cut or not, make another mark with the silver marker on the 

sidewall of the riser a distance of 

4 INCHES

 (3 INCHES for a LB-35 w/ 4” connections) above 

the edge just cut.  If you did not make a cut (meaning your riser height 

+ dimension from 

step 5

 line was beyond the bottom edge of your riser), still mark the sidewall of the riser 

4 INCHES above where your riser height 

+ dimension from step 5

 line would have been.  

DO NOT cut this new line.  Once the riser is installed into the main unit, this new line will end 

up at the top of the gasket and will aid in re-assembly.  See Figure 3.

    

8.   IMPORTANT:  Before the next step:

Make sure diffuser is installed inside the main unit at the appropriate location.

9.   Refer to sheet 1 of the installation instructions for leak/water testing procedures.

   

10. Take riser(s) and adapters apart to reduce the weight during installation.  Wipe all sidewalls and 

inside of gasket with a damp cloth to remove jobsite dust/debris.  Install components into the main 

unit starting from the lowest (cut) riser and working your way toward the finished floor level.  Upper 

clamps at each gasket need to be loosened or removed to aid in assembly.  Once riser(s)/adapter 

is inserted into gasket, upper clamp can be tightened.

      

11. Verify that the bottom of the lowest riser is protruding at least 2-1/2” but no more than 4” into 

the main unit from the top of the gasket.  Your mark from step 7 should be at the top edge

of the gasket on the main unit.  If measurements were made correctly, this should happen 

automatically.  See figure 4.

   

12.  If tilting of the adapter is required to be flush with finished grade, it must be done AFTER all 

clamps have been tightened with riser(s)/adaptor in a vertical and level position.  Tilting is 

achieved by using the flexibility of the gasket.  If tilting is done before clamps are tightened, a 

perfect gasket seal may be compromised.  Striem recommends tilting only the adapter versus the 

entire riser assembly to make sure your riser height is maintained.

   

13. Tighten all clamps to a minimum of 5 and a maximum of 8 ft lbs. of torque.  Use the same torque 

as you would tighten a rubber no-hub coupling.

   

14. The adapter must be adjusted 

upward

 to achieve certain extension heights.  See Table 2, 

Table 3 or Table 3a.

   

15. If jobsite riser height conditions change after the above steps have been completed, there 

may still be room for vertical adjustment in both directions.  As long as minimum and maximum 

overlaps are maintained (see Figure 4), the adapter/riser(s) can be adjusted/cut as many times 

as necessary.  Please follow these steps from the beginning to ensure the proper overlaps are 

maintained.

1.  Adjust 

adapter

 upwards to reach 22" to 24" 

2.  Adjust 

adapter

 upwards to reach 37" to 39"   

3.  Adjust 

adapter

 upwards to reach 56" to 58"

4.  Adjust 

adapter

 upwards to reach 70" to 72"

7.  Adjust 

adapter

 upwards to reach 19" to 21" 

8.  Adjust 

adapter

 upwards to reach 34" to 36"   

TeleGlide Riser (24 Series) Installation Guidelines

(LB-35, LB-50, LB-125, LB-275)

Call Striem with questions or suggestions @ 1-913-222-1500  Customer Service Hours: 8 AM-5 PM CST

LAB BASIN SERIES INSTALLATION,

OPERATION AND MAINTENANCE GUIDE

ECO:

10/22/18

MJ

REV:

DATE:

DWG BY:

DESCRIPTION:  

PROPRIETARY AND CONFIDENTIAL

THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF 

STRIEM, LLC. 

ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF 

STRIEM, LLC. 

IS 

PROHIBITED.

NOTES:

Striem Lab Basins are not to be installed in any other manner except as shown.  Consult local 

codes for separate trapping requirements, cleanout locations and additional installation instructions.

Vent required on outlet pipe only if outlet diptube is present.

SHEET NUMBER: 

5 of 6

Reviews: