After unpacking the rack, remove the front panel (6 screws) and the Earth
leads attached to it.
The rack(s) should be secured to the wall before installation
Power wiring:
Top
Control wiring:
Bottom
Borniers Alimentation Triphasé ou Mono
Wall
rack s are equipped with terminals f or Single or Three phase plus
Neutral and Earth connections.
24x2.5kW Wallrack
6x5kW Wallrack
Single Phase: 160A
Single Phase: 150A
T hr ee P ha se : 80 A T hr ee P ha se : 50 A
For single phase, there will be an optional single phase kit. The terminals
are provided for (2.5kW dimmers are 25 mm , 5kW dimmers are 32mm )
wires of the NEUTRAL and PHASE terminals.
Triphasé
Conductor sizes must be chosen to comply with local regulations and are
usually calculated to take into consideration cable lengths and types.
Typically, wiring for 3 PHASE LIVE conductors should be 25mm for
2.5kW dimmers and 32mm for 5kW dimmers maximum rack load
capacity.