background image

 

Order No.: 900220.020 

V2.24 

9/11

 

F7: Ventilator function at cooling operation 

At F7=1 the ventilator is always on (except possibly 
for a defrosting process, see parameter F4).  
At F7=2 the ventilator is always on or off together 
with the compressor. 
At F7=3 the ventilator is switched on whenever the 
compressor is on and the evaporator temperature 
(sensor F2) is below the refrigerating chamber 
temperature (sensor F1). The ventilator is switched 
off whenever the evaporator is switched off, whereas 
parameter F5 is not active. In the case of sensor 
error the ventilator reacts as in the setting F7=2. 
 

F8: Ventilator revolution number at normal 
cooling operation 

This parameter determines the ventilator revolution 
number at normal cooling operation. 
 

F9: Ventilator revolution number at defrosting 

This parameter determines the ventilator revolution 
number at defrosting. 

F10: Kick-start (in seconds) 

If necessary, this is an option to set a time during 
which the ventilator starts with the maximum number 
of revolutions for stable operation. This parameter is 
only efficient, if the ventilator is newly started. 
 

b1: Function key A 
b2: Function key B (if available) 

At setting = 0 the respective key has no function.  
At setting = 1 the controller is switched to standby 
mode 
At setting = 2 the key is linked with the function 
“setpoint Y1 for the thermostat 2 indicate/adjust” 
At setting = 3 a relay (indicated with parameter Ux) 
can be switched on or off directly with the key. In 
standby mode the key is locked and the 
corresponding relay switched off. After restarting the 
corresponding relay remains switched off. 
At setting = 4 a relay (indicated with parameter Ux) 
is switched despite of

 

the standby mode.

 

The 

condition of the exit is maintained until the key is 
pressed again or until it is changed by an external 
switching entrance. After net interruption, the 
condition before power failure is re-installed.  
At setting = 5 the actual value of sensor 2 can be 
indicated. At setting P4=0 the key has no function. 

 
b3: Function key 3 (standby) 

At setting b3=0 the function of the key can be 
deactivated. 
 

b11: Function external entrance E1 
b12: Function external entrance E2 
b13: Function external entrance E3 
b14: Function external entrance E4 

Depending on existing hardware there are no or not 
all external entrances. 
At setting = 1 the controller is switched to the 
standby mode. 
At setting = 2 defrosting of both controllers is started. 
At setting = 3 a relay (indicated with parameter Ux) 
is switched on or off directly. In standby mode it is 
locked and the relay is switched off. 
At setting = 4 a relay is switched directly (indicated 
with parameter Ux) regardless of the standby mode. 
After net interruption the condition before power 
failure is re-installed. 
 

U1: Exit connection K1 
U2: Exit connection K2 
U3: Exit connection K3 
U4: Exit connection K4

 

Depending on existing hardware there may not be 
all output relays. This parameter assigns the 
respective relay to the internal controller exits, to 
function key 1 or 2, to one external entrance or the 
buzzer.  
At setting =6 or =7 the relay is switched manually. It 
changes its condition with each pressure of the key 
and adopts the condition of the respective switching 
entrance whenever the latter changes. If the 
corresponding key or switching entrance has not 
been released for this function (see parameters b1, 
b2 and b11 to b14), the relay remains switched off. 
The buzzer connection in its function is comparable 
to the alarm connection. The buzzer, however, can 
be switched off with the DOWN key. 
 

L0: Own ST-Bus address 

Reserved for ST-Bus 
 

L40 :Mask for Low-Byte of Status 0 (ST-Bus) 

Reserved for ST-Bus 
 

Pro: Program version 

This parameter shows the program version. 

 

 
 
 
 

 
 

Summary of Contents for ST501-KU3KA.12P

Page 1: ...t is supplied with 230V AC and has four relay outputs as well as an exit for a DC voltage fan The relays can be used for different functions e g for a compressor a defroster an alarm relay etc see parameters U1 U4 The two resistance sensors seize the refrigerating chamber temperature and the evaporator temperature Sensor PTC Range 55 99_C Front size 106mm x 68mm Panel cut out 87 5mm x 56 5mm Tight...

Page 2: ...Order No 900220 020 V2 24 2 11 ...

Page 3: ...n addition the SET key is used for setting parameters Key 6 Standby With this key the controller is switched to standby mode Pressing the key a second time restarts the unit The key can be deactivated by setting the respective parameter see parameter b3 First control level Parameter setting for the main setpoint If none of the keys is pressed the display indicates the actual value of the temperatu...

Page 4: ...s Access to the third control level is granted when selecting parameter PA on the second control level Parameter PA is to be set at 19 Then the key UP and DOWN have to be simultaneously pressed for approx 4 seconds which will give access to the third control level beginning with parameter P0 With the keys UP and DOWN you can scroll the list in both directions Pressing the SET key will give you the...

Page 5: ... 150 C 10 C 5 0 C d3 Defrosting time limit 1 99 min 30 min 20 min d6 Indication of the refrigerating chamber temperature during defrosting 0 actual temperature 1 temperature determined just before the start of defrosting 1 d7 Drainage time 0 15 min 2 min 0 min A0 Hysteresis for alarm 1 15 K 2 K 5 K A1 Minimum limit value 99 0 0 1 K 0 inactive 10 K A2 Maximum limit value 0 1 99 0 K 0 inactive 10 K ...

Page 6: ...y switched off in standby mode 4 relay directly regardless of standby mode 0 b12 Function switching input E2 see b11 0 b13 Function switching input E3 if available see b11 0 b14 Function switching input E4 if available see b11 0 U1 Exit connection K1 0 no connection 1 connection to compressor 2 connection to defrost 3 connection to ventilator 4 connection to alarm 5 connection to thermostat 2 6 co...

Page 7: ...y how many measured values an average value is to be formed r0 Hysteresis for the compressor contact Parameter r0 sets the temperature margin between switching off and switching on of the compressor A small hysteresis permits a more exact regulation however also leads to more frequent switching of the compressor The hysteresis is set one sided above the setpoint r1 Setpoint limitation minimum r2 S...

Page 8: ...ysteresis for alarm The hysteresis of the alarm contact is asymmetrically set downward at the maximum alarm value upward at the minimum alarm value A1 A2 Minimum maximum limit values The limit values serve for monitoring of the refrigerating chamber temperature They are relative i e going along with the setpoint S1 of the refrigerating chamber Alarm is released when exceeding maximum limit value o...

Page 9: ...key is pressed again or until it is changed by an external switching entrance After net interruption the condition before power failure is re installed At setting 5 the actual value of sensor 2 can be indicated At setting P4 0 the key has no function b3 Function key 3 standby At setting b3 0 the function of the key can be deactivated b11 Function external entrance E1 b12 Function external entrance...

Page 10: ...c3 1 the controller operates in timed defrosting modus defrosting time as set in d3 At setting c3 2 see parameter Y6 EP Data loss at parameter memory basic contact 1 and 2 are dead If error cannot be eliminated by switching on off the controller must be repaired Error message E0 E1 and EP changes in the display with the actual value of sensor F1 unless the latter is defective This happens independ...

Page 11: ... A 250V normally open contact function see U3 K4 Relay 16 2 2 A 250V normally open contact fan voltage output for DC fan 0 24V max 800mA corresponds 20W Display One 3 digit LED Display height 13 mm for temperature indication Three LEDs diameter 3mm for status display of the outputs Power supply 230V 50 60Hz power consumption max 40 VA Connectors Cage clamp 5 x 3 pole for cable up to 2 5mm Cage cla...

Reviews: