Buttons and switching inputs
(password-protected)
Para-
meter
Description of function
Setting range
Values
default
Function button T1
0: without function
1:controller on/standby
2:defrosting request
3:acknowledge alarm
4:relay function light 1, not active in standby
5:relay function light 1, regardless of standby
6:relay function light 2, not active in standby
7:relay function light 2, regardless of standby
8:relay function window heating, not active in standby
9:relay function window heating, regardless of standby
10:relay function blade scraper, not active in standby
11:relay function blade scraper, regardless of standby
12:relay function door frame heating, not active in standby
13:relay function door frame heating, regardless of standby
14:relay function F, not active in standby
15:relay function F, regardless of standby
16:Set1 / Set2 change-over
17:day / night change-over
18:"super-frost“ on/off
19:evaporator fan on permanently
20:control circuit 1 on/off
21:control circuit 2 on/off
22:set for setpoint Y1
23:display MIN
24:display MAX
25:display sensor F1
26:display sensor F2
27:display sensor F3
28:display sensor F4
29:display sensor F5
30:reset both MIN/MAX
31:reset MIN
32:reset MAX
33: Set time
34: Set date
35: like 22 + switch indication)
36: like 16 + remember condition
37: like 5 + remember condition
38: like 7 + remember condition
2
Function button T2
see
3
Function button T3
see
0
Function button T4
see
0
Function button T5
see
0
Function button T6
see
1
Function button T7
see
0
Function button T8
see
0