StoneL publication 105406revA
7 QZ 70 en
Quartz |
17
Applicable models
QN45_, QX45_
Specifications
Configuration
(2) NAMUR sensors (EN 60947-5-6)
Wire terminals for one or two solenoids
Voltage range
5 - 25 VDC
Current ratings
Target present
Target absent
Current < 1.0 mA (LED = OFF)
Current > 3.0 mA (LED = ON)
LED indication
Bottom sensor: green
Top sensor: red
Temperature range
-40° to 80° C
Operating life
Unlimited
Warranty
All mechanical parts
Two years
Sensor module
Five years
Use with intrinsically safe repeater barrier. NAMUR sensors conform to EN 60947-5-6 standard.
Bench test procedure
Use StoneL Light Read Tester or use a 24 VDC power supply. No series
load resistor required.
TOP SW LED
(red)
BTM SW LED
(green)
SOL +
SOL -
SOL PWR +
SOL PWR -
TOP SW +
TOP SW -
BTM SW +
BTM SW -
Models with 3 conduit entries have
an additional 2-pole terminal block
for second solenoid termination
SOL
PWR
2
1
SOL PWR +
SOL PWR -
SOL +
SOL -
Wiring diagram
4.2
Intrinsically safe inductive proximity switches
4.2.2
Dual module NAMUR sensors (45)
Touch & Tune switch setting
All adjustments assume you are looking down on the top of the
sensor module. The magnet in the cam will be centered on the sensor
when activation occurs. When the cam is released be sure it slides fully
onto the spline. One spline tooth setting is 4 1/2°.
Valve closed to open in counterclockwise rotation (Fig. 1)
1. With the valve in the closed position, set the bottom cam by lifting
up off the splined collar rotating so that the magnet is centered on
the bottom sensor and the top cam is 90° from the bottom cam.
2. At this time the red LED will be lit and green LED out.
3. Move valve counterclockwise to the open position. Green LED will
be lit and red LED will be out. If the red LED is lit, push down top
cam and rotate until magnet in the top cam is centered on the
top sensor and the red LED goes out. Cam adjustments are now
completed.
Valve closed to open in clockwise rotation (Fig. 2)
1. With the valve in the closed position, set the bottom cam by lifting
up off the splined collar rotating so that the magnet is centered on
the bottom sensor and the top cam is 90° from the bottom cam.
2. At this time the red LED will be lit and green LED out.
3. Move valve clockwise to the open position. Green LED will be
lit and red LED will be out. If the red LED is lit, push down top
cam and rotate until magnet in the top cam is centered on the
top sensor and the red LED goes out. Cam adjustments are now
completed.
Notes
1. With the valve in the closed position, the red LED is lit and the
bottom sensor is active (i.e. drawing less than 1.0 mA of current),
while the top sensor is inactive (i.e. drawing greater than 3.0 mA of
current).
2. When the valve is in the open position, the green LED is lit and the
top sensor is active while the bottom sensor is inactive.
3. During valve transition from closed to open or open to closed
both LEDs will be lit and neither sensor will be active.
Caution:
To prevent ignition of hazardous atmospheres,
replace cover before energizing the electrical circuits. Keep
cover tightly closed within operation.
Fig. 1 cam set for
counterclockwise
rotation
Fig. 2 cam set for
clockwise rotation
Reference controlled installation drawing #105193 for
proper intrinsic safety installation details. Find document
in the Appendix on page 49 or at
www.stonel.com/en/
products/quartz/installation-manuals
STOP