8 | Commissioning
STOBER
34
11/2019 | ID 442710.03
8.2.6
Transmitting a project configuration
Transmit the full project configuration to your IO controller.
ü
You have mapped and parameterized all nodes of your physical PROFINET IO system in your TIA project.
1.
Project tree
>
Devices
tab:
Mark the folder with the IO controller in question.
2.
Select
Online
>
Download to device
in the menu bar.
ð
The
Extended download to device
window opens.
3.
Compatible devices in target subnet
area:
Click on
Start search
.
ð
All IO controllers of the defined subnet are listed.
4.
Mark the IO controller in which you would like to save the project configuration and click
Load
.
If multiple IO controllers are in your subnet, you can test your selection beforehand by verifying the selected
controller using
Flash LED
.
ð
The project configuration is transferred to the selected IO controller.
8.2.7
Testing communication
Check for error-free communication between the IO controller and IO devices.
ü
You have transferred the project configuration to the IO controller.
1.
Project tree
>
Devices
tab:
Open the folder of the controller in question >
Online & diagnostics
>
Online access
.
ð
This switches you to the respective device view.
2.
Verify the active IO controller and click on
Go online
.
ð
An online connection to the selected IO controller is established.
3.
Click on
Diagnostics
>
Diagnostics buffer
.
4.
Events
area:
The diagnostics buffer is part of the IO controller's system memory. Possible error messages are output here. If an
error message is not present, communication in your PROFINET IO system is free of errors.
ð
The connection between IO controller and IO devices is projected and data exchange is possible.