8 | Commissioning
STOBER
32
11/2019 | ID 442710.03
8.2.4
Configuring the IO controller
As needed, you can change the pre-configured IP address and subnet address of the IO controller.
ü
You are in the TIA network view.
1.
Double-click on the IO controller of your IO system.
ð
This switches you to the respective device view.
2.
Select
General
tab >
General
>
PROFINET interface
>
Ethernet addresses
in the device properties.
3.
IP protocol area:
Set IP address in the project
: Activate this option if it is not active by default and change the IP and subnet addresses
of the IO controller.
ð
IP and subnet address are reconfigured.
8.2.5
Configuring IO devices
In this step, specify the data volume to be transmitted for every IO device of your PROFINET IO system and name the IO
devices according to PROFINET naming conventions.
If the respective IP addresses of the IO devices should not be assigned automatically by the IO controller, modify the default
addresses. You also have the option to configure the monitoring of the IO data exchange.
Defining transmission volumes
ü
You are in the TIA network view. The hardware catalog is open.
1.
Double-click on an IO device in your IO system.
ð
This switches you to the respective device view.
2.
Hardware catalog
:
Select
Catalog
>
Module
.
ð
There are two categories available that determine the data volumes generally to be transmitted.
3.
Select a module with a data volume that corresponds to your process data map in the drive controller. Mark this
module and drag and drop it onto the
Device overview
tab > Line/slot 1 and slot 2.
ð
The input and output addresses of the IO device are generated automatically.
Assigning device names
1.
Double-click on an IO device in your IO system.
ð
This switches you to the respective device view.
2.
Device view
:
Double-click on the IO device graphic.
3.
Device properties
:
Select the
General
tab.
4.
General
area:
Name
: Name the IO device according to PROFINET naming conventions.
5.
Device view
:
Mark the IO device in question and select
Assign device name
using the context menu.
ð
The
Assign PROFINET device name
window opens.