Bus diagnosis/LEDs
Operation manual
ID 441687.04
WE KEEP THINGS MOVING
23
6
6
Bus diagnosis/LEDs
The DP 5000 option module is equipped with a green and a red LED. The LEDs
indicate communication-specific states. This permits the PROFIBUS status to be
diagnosed on the device.
Fig. 6-1 View on LED
The following diagnostic capabilities are available:
•
The two LEDs on the option board DP 5000
•
Parameter
A84 PROFIBUS Baudrate
Red LED Green
LED
Bedeutung/Maßnahme
Off
Off
No connection between the inverter and the PROFIBUS
board (board was not recognized or has failed. See
parameter
E54 option module 1
).
Flashing Off
PROFIBUS master stopped bus for more than 25 s (PLC in
stop) or has failed or bus cable no longer connected (see
parameter
A84 PROFI-Baud
).
Off
Flashing Device is ready and is waiting for the PROFIBUS master to
start or:When this state does not change although the
PROFIBUS master has already attempted to establish a
connection, this means that the applicable function blocks
for PROFIBUS have not been downloaded to the inverter.
Off
On
Device was configured by PROFIBUS master and data
communication was started.
Flashing Flashing PROFIBUS master stopped the bus just a few seconds ago
(< 25 s) (PLC in stop) or has failed or bus cable is no longer
connected (see parameter
A84 PROFI-Baud
).