4. Clear Text Display Module & System Parameters
© STÖBER plc 1998
05.02.01
26
Parameter Function
Range
[Default]
Description / Notes
P203
••••
I
gain (%)
0.00 -
99.99
[0.00]
Integral gain.
0.01% corresponds to the longest integral response time.
P205
••••
Sample interval (x 25 ms)
1 - 2400
[1]
Sampling interval of feedback sensor.
P206
••••
Transducer filtering
0 - 255
[0]
0
=
Filter off.
1
-
255
= Low pass filtering applied to transducer.
P207
••••
Integral capture range (%)
0 - 100
[100]
Percentage error above which integral term is reset to zero.
P208
Transducer type
0 - 1
[0]
0
= An increase in motor speed causes an increase in sensor
voltage/current output.
1
= An increase in motor speed causes a decrease in sensor
voltage/current output.
P210
Transducer reading (%)
0.0 - 100.0
[-]
Read only. Value is a percentage of full scale of the PI input.
P211
••••
0% setpoint
0.00-
100.00
[0.00]
Value of P210 to be maintained for 0% setpoint.
P212
••••
100% setpoint
0.00-
100.00
[100.00]
Value of P210 to be maintained for 100% setpoint.
P220
••••
PI frequency cut-off
0 - 1
[0]
0
= Normal operation
1
= Switch off inverter at or below minimum frequency.
P331
Analogue mode
0 - 4
[2]
0
= Internal potentiometer only
1
= External analogue input only
2
= Internal potenti external analogue input
3
= Internal potentiometer fine, external input coarse
4
= Internal potentiometer coarse, external input fine
P332
Fine adjustment (%)
0 - 100
[10]
Percentage of fine tuning adjustment for P331 = 3 or 4.
P700
P701
••••
P702
P723
State of digital inputs
0 - 7
[-]
DIN3
DIN2
DIN1
0
=
0
0
0
1
=
0
0
1
2
=
0
1
0
3
=
0
1
1
4
=
1
0
0
5
=
1
0
1
6
=
1
1
0
7
=
1
1
1
P880
Specific to PROFIBUS-DP. See PROFIBUS Handbook for further
details. (Access only possible with P099 = 1.)
Specific to PROFIBUS-DP. See PROFIBUS Handbook for further
details. (Access only possible with P099 = 1.)