INSTRUCTION MANUAL 

 

GB

 

– 

3/5 

www.stifnet.com

 - DOC NO. BE0455062-B 

 

 

 
 

Electrically connect the VIGIRO SV26® by respecting the electrical scheme B or C and the operating conditions 
depending on the version used, 2-wire or 3-wire: 

 
 

PROGRAMMATION 

Application of the previously defined underspeed threshold -33%, -20%, -11% or -6% in advance to stop the handling 
equipment in a proven fault situation. 

1)  Remove the access screw to the learning button with the upper part of the screwdriver (available on the base of 

the VIGIRO SV26

®

), then store the access screw in a safe place during all learning stages. 

2)  Run the handling equipment until a stable speed is reached. 

3)  Switch on the VIGIRO SV26

®

4)  The first learning step is to record the rated speed of the handling device, to do this insert the narrow end of 

the screwdriver into the access hole then press and hold the button until the green LED goes out for 3 seconds, 
when the green LED comes back on release the button. 

The green LED flashes slowly and then lights up to indicate that the speed learning is successful. 

 
At  this step, the default  underspeed threshold is -33% (e.g.  if  the nominal speed  is  180 rpm, the detector 
output will be deactivated when the underspeed is reduced below the threshold 

120 rpm). 

 

5)  After learning the nominal speed (active underspeed -33%), it is possible to fine-tune the underspeed setting 

by programming a more restrictive threshold at -20%, -11% or -6%. 
 
The  underspeed  thresholds  of  -20%,  -11%  or  -6%  are  available  by  performing  one  training  session  after 
another. For example, it takes three successive learnings to reach the -6% threshold. 

 
 

2-wire branch scheme C 

Coulours 
BN = Brown 
BU = Blue 
GR = Green (not used)
 

 

        
 
PVC cable 2m non-ATEX

 

zone 2x0.34mm²

 

3-wire/NC connection scheme B 

 Colours  
BN   = Brown 
BU   = Blue 
WH = White 
BK   = Black (Do not used) 
        
 

 

PVC cable 2m for ATEX area

 

and not

 

ATEX 3x0.34mm²

 

For low voltage sensor, ATEX or not 

-

 

3-wire cable connection 

-

 

L=2m cable  

-

 

Voltage 12-24V DC 

-

 

Voltage limits, including ripple, 10-36V DC 

-

 

Switching power ≤

 1

00mA 

-

 

temperature Operating: -25... 70°C 

-

 

temperature Operating: -20... 60°C (ATEX) 

-

 

Protection - IP67 

 Caution: Any connection must be made outside the 

ATEX zone 

For multi-voltage sensor, out of ATEX zone 

-

 

2-wire cable connection 

-

 

L=2m cable 

-

 

Voltage 24... 240V AC/DC 

-

 

Voltage limits, ripple included 20... 264V AC/DC 

-

 

Residual voltage at nominal I ≤5.5V 

-

 

Switching power 5... 1.00 mA AC/DC 

-

 

temperature Operating: -25... 70°C 

-

 

Protection - IP68 

 It is imperative to put in series with the load a 

fast-acting fuse of 0.4A 

WH/2 (NC) 

Summary of Contents for VIGIRO SV26

Page 1: ...ecting cable 2m or 3 wires 3 Standard M12 threaded rotation axis M10 on request for fixing at the end of the shaft 4 Anti rotation strap 5 Detectable 2 blade propeller optional 4 blade propeller located inside the protection 6 Transparent window 7 Programming button access screw 8 SENSOR screwdriver Possible adjustment of the VIGIRO SV26 Rotation frequency to respect 0 5 500 rpm or 1 1000 pulses m...

Page 2: ...a standstill off before any installation or intervention on the VIGIRO SV26 intervention information to be indicated on the machine Optional magnetic fixation without tapping The EAZY FIX can t be installed on a stainless steel shaft Ensure that the bearing surface of the shaft is clean and plane Take precaution during installation of the EAZY FIX because its very strong magnetic force of attracti...

Page 3: ...s 180 rpm the detector output will be deactivated when the underspeed is reduced below the threshold 120 rpm 5 After learning the nominal speed active underspeed 33 it is possible to fine tune the underspeed setting by programming a more restrictive threshold at 20 11 or 6 The underspeed thresholds of 20 11 or 6 are available by performing one training session after another For example it takes th...

Page 4: ... or a new speed please repeat all the programming steps starting with a reset 1 To perform the Reset please press and hold the button until the green LED goes out for 3 seconds when the green LED lights up again continue to hold the button for 4 seconds until the green LED goes out and then release the button The detector is now without an underspeed program programmable underspeed 33 by default a...

Page 5: ...s found you must proceed with the restoration in order to correct the defect s before you can use the bucket lift or belt conveyor again 4 Only personnel trained and authorized in maintenance procedures forequipment are able to carry out inspections of the VIGIRO SV26 5 The output of the VIGIRO SV26 remains closed for 9 seconds to allow the handling equipment to reach its rated speed DISPOSAL When...

Reviews: