INSTRUCTION MANUAL
GB
–
3/3
- N° DOC BE0455060-A
- Electrically connect the
VIGIRO
®
IP26 according to the appropriate diagram
.
PERIODIC CHECKS & MAINTENACE
- To guaranty the operational integrity of the VIGIRO IP26
®
, you must plan periodical inspections. The frequency of
the inspections lust be enough to avoid any dangerous situations (situations that could have an incidence for the
intrinsic functioning of the VIGIRO IP26
®
).
- During those inspections, check that the VIGIRO IP26
®
is not affected by the following defect: dust layer > 2mm,
VIGIRO IP26® shaft fixing loose, degraded or loose anti-rotation strap, power-on LED not operational, degraded
electrical wiring, shock on the VIGIRO IP26
®
casing, etc …
- In the case of one or multiple defects, you must carry the repair in order to correct the defect(s) before you can
use the bucket elevator or the belt conveyor again
- Only personnel trained and authorized in the maintenance procedures for this equipment are able to carry out
inspection of the VIGIRO IP26
®
.
SCRAPPING
When dismantling the VIGIRO IP26
®
, the user must ensure that this device is properly disposed of and hand over to
specialized collection centres the components according to their nature (stainless steel, electrical equipment, seals, etc.).
In the event that the VIGIRO IP26® is used, controlled, under conditions contrary to the precautions described in this
instruction manual, STIF declines all responsibility for damage caused to humans, animals, the environment or property.
materials
2 wires connection diagram / NC
Colours
BN = Brun
BU = Blue
PVC cable 2m 2x0.34mm²
3 wires connection diagram / NC
Colours
BN = Brun
BU = Blue
BK = Black
PVC cable 2m for ATEX and non ATEX zones
3x0.34mm²
For low tension sensor, ATEX or not
-
Connection by 3-wire cable
-
Cable L=2m
-
Voltage 12-24V DC
-
Voltage limit, including ripple, 10-36V DC
-
Switching power
≤
100 mA
-
Operating temperature: -
25…70°C
(non ATEX)
-
20…60°C
(ATEX)
-
Protection - IP67
Warning: All connections must be made outside the
ATEX zone
For multi-voltage sensor, outside ATEX zone
-
Connection by 2-wire cable
-
Cable L=2m
-
Voltage
24…240V AC/DC
-
Voltage limit, including ripple, 20
…264V AC/DC
-
Residual voltage at I
nominal ≤
5.5V
-
Switching power
5…200 mA AC/DC
-
Operating temperature: -
25…70°C
-
Protection - IP68
It is imperative to put in series with the load a fast-acting
fuse of 0.4A