background image

INSTRUCTION MANUAL

 

 

GB

 

 

3/3 

www.stifnet.com

 - N° DOC BE0455060-A 

 
- Electrically connect the

 VIGIRO

®

 IP26 according to the appropriate diagram

 

 
 

PERIODIC CHECKS & MAINTENACE 

-  To guaranty the operational integrity of the VIGIRO IP26

®

, you must plan periodical inspections. The frequency of 

the  inspections  lust be enough to avoid any dangerous situations (situations that  could  have an incidence  for the 
intrinsic functioning of the VIGIRO IP26

®

). 

-  During  those  inspections, check that the  VIGIRO IP26

®

 is not affected  by the following defect: dust layer >  2mm, 

VIGIRO  IP26®  shaft  fixing  loose,  degraded  or  loose  anti-rotation  strap,  power-on  LED  not  operational,  degraded 
electrical wiring, shock on the VIGIRO IP26

®

 

casing, etc … 

-  In the case of one or multiple defects, you must carry the repair in order to correct the defect(s) before you can 

use the bucket elevator or the belt conveyor again  

-  Only  personnel  trained  and  authorized  in  the  maintenance  procedures  for  this  equipment  are  able  to  carry  out 

inspection of the VIGIRO IP26

®

 

SCRAPPING 

When  dismantling  the  VIGIRO  IP26

®

,  the  user  must  ensure  that  this  device  is  properly  disposed  of  and  hand  over  to 

specialized collection centres the components according to their nature (stainless steel, electrical equipment, seals, etc.). 

 

In the event that the VIGIRO IP26® is used, controlled, under conditions contrary to the precautions described in this 
instruction manual, STIF declines all responsibility for damage caused to humans, animals, the environment or property. 

materials 

2 wires connection diagram / NC 

Colours 

BN = Brun 

BU = Blue 
 

 

        

 
 

PVC cable 2m 2x0.34mm²

 

3 wires connection diagram / NC 

 Colours  

BN = Brun 

BU = Blue 
BK = Black 

        

 

 

 

 PVC cable 2m for ATEX and non ATEX zones 

 

3x0.34mm²

 

For low tension sensor, ATEX or not 

-

 

Connection by 3-wire cable 

-

 

Cable L=2m  

-

 

Voltage 12-24V DC 

-

 

Voltage limit, including ripple, 10-36V DC 

-

 

Switching power 

≤ 

100 mA 

-

 

Operating temperature: -

25…70°C

 (non ATEX) 

 -

20…60°C

 (ATEX) 

-

 

Protection - IP67 

 Warning: All connections must be made outside the 

ATEX zone 

For multi-voltage sensor, outside ATEX zone 

-

 

Connection by 2-wire cable 

-

 

Cable L=2m 

-

 

Voltage 

24…240V AC/DC

 

-

 

Voltage limit, including ripple, 20

…264V AC/DC

 

-

 

Residual voltage at I 

nominal ≤

5.5V 

-

 

Switching power 

5…200 mA AC/DC

 

-

 

Operating temperature: -

25…70°C

 

-

 

Protection - IP68 

 It is imperative to put in series with the load a fast-acting 

fuse of 0.4A 