ALARMS
ALARM STATUS
Main alarm
(on/off).
Set the “off” slider to the
position in order to temporarily switch
off the main alarm (siren). All the alarms will be blocked temporarily.
This does not apply to the hardware alarms; they cannot be switched
off temporarily. The main alarm is switched off for 30 minutes (the
LED bar is flashing red irregularly). The main alarm is switched on
automatically again after 30 minutes. The alarm relay will de-energize
again, causing an alarm, if the cause of the alarm has not been
removed.
Clear delay time: set the “off” slider to the
position.
Test the operation of the alarm relay (siren). Set the “Test” slider to the
position to activate the alarm relay (siren) for 120 seconds. Clearing
the alarm test time: Set the “Test” slider to the
position.
Display of alarm cause and alarm control (and possibly the terminal number
or address).
An alarm has occurred for an external device (KLD-100 or KLC-100); the text
is followed by the device address.
NEVER FORGET TO SWITCH AN ALARM “ON” AGAIN AFTER IT WAS SWITCHED OFF (e.g. in order to
remedy a malfunction). Failing to switch the alarm back on may have adverse effects for people, animals,
equipment or property.
Preferably use the Off function to remedy a malfunction.