Stienen B.E. KL-6400 Series User Manual Download Page 17

 

Page 17 of 28 

MISCELLANEOUS 

COOLING (ON/OFF) 

 

 

 

 

Setting the cooling is identical to 

setting the room heating. To prevent 

the humidity in the room from 

becoming too high due to cooling, 

the RH can switch off the cooling.  

 

If the relative humidity rises to above the preset value + hysteresis, the cooling will be switched off. If the RH 

falls to below the preset value afterwards, the cooling will be switched on again. The default hysteresis setting is 

2%. 

 

You can use the “Soaking” function when the room status is “out of operation” or “cleaning”. The cooling system 

will then be run at full capacity (100%) for the “Period ON” time. As soon as the room status changes, “Soaking” 

will be switched “OFF” to prevent the soaking starting immediately after you put the room “out of operation”. 

 

Soaking 

Options 

 

 

 

Compensation maximum 

ventilation 

If the current cooling is “on” 

(switched on), you can have the 

maximum room ventilation lowered 

by the percentage set for “Compens. 

maximum vent.” to increase the 

cooling effect. 

 

TEMPERATURE MONITORING 

 

The temperature monitoring function is activated by your installer. 

 

The current measurement of each sensor is compared with the 

measurement of one minute ago. 

If the temperature increase in that minute is equal to or greater than the 

relative alarm limit, an alarm is given. If the measurement is within the 

limits, the previous measurement is made equal to the current 

measurement and a new measurement is started. 

 

If the temperature measured by the sensor increases to above the 

absolute limit, an alarm is given as well. 

 

The temperature monitoring alarm is only given if a positive difference is 

detected. 

 

 

 

 

SENSORS 

 

 

 

Selecting a sensor displays a table 

with the minimum and maximum 

sensor temperatures for the past 

week. The table also states the times 

when the minimum and maximum 

temperatures occurred on the 

various days. 

 

Your installer can change the sensor names to any name of a maximum of 15 characters. 

1 minute 

Current 

measuremen

Measurement of 

1 minute ago 

Difference in  

temp. 

Summary of Contents for KL-6400 Series

Page 1: ...USER MANUAL CLIMATE COMPUTERS KL 6400 series EN StienenBE KL 6400 G EN02000...

Page 2: ...our Customer Service Department if you have any questions Be sure to have all necessary data at hand To ensure a speedy solution to the malfunction and to avoid any misunderstandings it is advisable...

Page 3: ...ting 16 Miscellaneous 17 Growth curves 18 Overviews 20 Alarm 21 Communication alarm 21 Climate alarm codes 22 ROOM STATUS 24 SENSORS 25 Outside temperature alarm 25 ALARM 26 Latest alarm for device 26...

Page 4: ...If the sensor is connected via a fixed socket outlet FSO push on the flap of the fixed socket outlet until you hear it click lock Application notes Central ventilation KL64CV N ENxxxxx Compensations...

Page 5: ...6401 KL 6402 KL 6405 KL 6410 Whenever a key is pressed the display will be lit for a couple of seconds so that you can also see the settings and measurements in a dark animal house Note Only press the...

Page 6: ...r is in room 4 and you press the key the cursor will remain in room 4 Alarm key Short key for alarm screens Test alarm test This enables you to test the operation of the alarm relay siren If you enter...

Page 7: ...e with the table below The serial number must be between 01 and 99 00 means that the input output is not in use I O type Letter Serial number Explanation 0 10V output A 1 99 Analogue output with a ran...

Page 8: ...confirm Menu option Start change Confirm change The cursor is displayed as a green rectangle e g While a change is being made the cursor is displayed as a black border e g TEMPERATURE SETTINGS With a...

Page 9: ...in use Cleaning room Cleaning room Pre heating room Pre heating room Measuring fan switched off Measuring fan switched off Cooling on Cooling on Room heating on Room heating on Room heating switched...

Page 10: ...sed users from changing settings on your climate computer you can have your installer set an access code An access code consists of a combination of 4 digits You can have a maximum of 6 access codes s...

Page 11: ...to 7 C depending on the outside temperature is to be advised Minimum and maximum ventilation If compensation depending on the fill ratio has been installed the minimum and or maximum ventilation will...

Page 12: ...above 100 This will result in the minimum and maximum ventilation being increased without you having to adjust other settings Minimum and maximum ventilation The fill ratio is used to calculate the m...

Page 13: ...the flap Outside temperature Current outside temperature Frost protection Current status of frost protection active off Cycle time Current cycle time Flaps Current flap status auto open close Compensa...

Page 14: ...g the room status to Cleaning and Not in use enables you to manually enter the desired ventilation percentage when cleaning the room at Manual control percentage setting and calculated percentage are...

Page 15: ...inlet flap temperature setting 3 0 C Bandwidth 4 0 C Minimum flap opening 15 Maximum flap opening 100 Minimum and maximum flap opening If desired you can restrict the minimum and maximum flap position...

Page 16: ...average of these temperature sensors If a sensor is defective it will be left out of the average calculation and the heating will continue to control on the basis of the remaining temperature sensors...

Page 17: ...lowered by the percentage set for Compens maximum vent to increase the cooling effect TEMPERATURE MONITORING The temperature monitoring function is activated by your installer The current measurement...

Page 18: ...urve of the setting you want to change is active you can only change the relevant setting by changing the setting of the curve The settings obtained from a growth curve are recalculated every hour to...

Page 19: ...INLET FLAP 1 Minimum flap opening Maximum flap opening You can only set the growth curve for the temperature with an air inlet flap which controls on the basis of temperature AIR INLET FLAP 2 Setting...

Page 20: ...h the minimum and maximum temperatures of the past week of the temperature selected will be shown The table also states the times when the minimum and maximum temperatures occurred on the various days...

Page 21: ...and NOT IN USE states influence the alarm operation Installation errors such as Output already assigned Incorrect output type Input already assigned etc have to be solved first before putting the syst...

Page 22: ...E You can set the alarm limits for the room temperature here If temperature compensation is active the maximum alarm limit can be adjusted by means of the corrected Temperature setting If an outdoor s...

Page 23: ...or you can switch the inlet temperature alarm on or off in this screen The current inlet temperature is shown next to the alarm status Cooling Temperature monitoring Switching off the temperature moni...

Page 24: ...or the following temperature measurements room temperature inlet temperature with inlet heating with frost protection floor temperature Pre heat All heatings are controlled except the inlet heating wh...

Page 25: ...temperatures of the past week The table also states the times when the minimum and maximum temperatures occurred on the various days If the climate computer has its own outside temperature sensor this...

Page 26: ...used the alarm relay to de energize due to an alarm condition in the relevant room are saved per room The cause of the alarm is displayed in addition to the date and time Alarm 0 The cause of the most...

Page 27: ...ess of the active situation here operating mode off You can set the sleep mode brightness here On time Number of seconds during which the screen is lit after the last time a key is pressed Setting 0 s...

Page 28: ...ad to draughts and in summer they can result in unwanted heating due to hot air being drawn in from between the roof and the insulating materials for example This will require the fans to work extra h...

Reviews: