Page 17 of 28
MISCELLANEOUS
COOLING (ON/OFF)
Setting the cooling is identical to
setting the room heating. To prevent
the humidity in the room from
becoming too high due to cooling,
the RH can switch off the cooling.
If the relative humidity rises to above the preset value + hysteresis, the cooling will be switched off. If the RH
falls to below the preset value afterwards, the cooling will be switched on again. The default hysteresis setting is
2%.
You can use the “Soaking” function when the room status is “out of operation” or “cleaning”. The cooling system
will then be run at full capacity (100%) for the “Period ON” time. As soon as the room status changes, “Soaking”
will be switched “OFF” to prevent the soaking starting immediately after you put the room “out of operation”.
Soaking
Options
Compensation maximum
ventilation
If the current cooling is “on”
(switched on), you can have the
maximum room ventilation lowered
by the percentage set for “Compens.
maximum vent.” to increase the
cooling effect.
TEMPERATURE MONITORING
The temperature monitoring function is activated by your installer.
The current measurement of each sensor is compared with the
measurement of one minute ago.
If the temperature increase in that minute is equal to or greater than the
relative alarm limit, an alarm is given. If the measurement is within the
limits, the previous measurement is made equal to the current
measurement and a new measurement is started.
If the temperature measured by the sensor increases to above the
absolute limit, an alarm is given as well.
The temperature monitoring alarm is only given if a positive difference is
detected.
SENSORS
Selecting a sensor displays a table
with the minimum and maximum
sensor temperatures for the past
week. The table also states the times
when the minimum and maximum
temperatures occurred on the
various days.
Your installer can change the sensor names to any name of a maximum of 15 characters.
1 minute
Current
measuremen
t
Measurement of
1 minute ago
Difference in
temp.