background image

iNSTALLATiON 

 

installation

www.stiebel-eltron.com 

WPL  47 | WPL  57 | 

11

10.5  Filling the heating system

Carry out a fill water analysis before filling the system. This may, 

for example, be requested by the relevant water supply utility.

!

 

Material losses

To avoid damage as a result of scaling, it may be neces-

sary to soften or desalinate the fill water. Always observe 

the fill water limits specified in the "Specification / Data 

table" chapter.

 

f

Recheck these limits 8-12 weeks after commission-

ing and as part of the annual system maintenance.

 

Note 

With a conductivity > 1000 μS/cm, desalination treatment 

is recommended in order to avoid corrosion.

 

Note 

Suitable appliances for water softening and desalinating, 

as well as for charging and flushing heating systems, can 

be obtained via trade suppliers.

 

Note 

If you treat the fill water with inhibitors or additives, the 

same limits apply as for desalination.

 

f

Fill the heating system via the filling nozzle installed on site.

 

f

After filling the heating system, check the connections for 

leaks.

10.5.1  Venting the heating system

 

f

Vent the pipework carefully. For this, also activate the air 

vent valve integrated into the heating flow inside the heat 

pump.

10.6  Minimum flow rate

The minimum flow rate is set via the temperature differential of 

the buffer circuit.

 

f

Set the buffer charging pump so that the value is equal to or 

lower than the maximum temperature differential. See the 

chart “Maximum temperature differential on the heating side 

with buffer cylinder”.

You can set the flow rate in heat pump mode. In order to do this, 

firstly make the following settings:

 

f

Temporarily remove the fuse from the electric emergency/

auxiliary heater to isolate the emergency/auxiliary heater 

from the power supply. Alternatively, switch OFF the second 

heat generator.

 

f

Operate the appliance in heating mode.

 

f

In the menu “SETTINGS / HEATING / STANDARD SETTING”, 

set parameter “BUFFER OPERATION” to “ON”.

The flow rate can be adjusted using the temperature differential 

of the buffer circuit. The value must not fall below the minimum 

flow rate.

Maximum temperature differential on the heating side with buffer 

cylinder:

1

10 

-15  -10 

-5 

10 

15 

20 

25 

30 

D

00000

63

55

0

1  Nominal flow rate

X  Outside temperature [°C]

Y  Maximum temperature differential [K]

 

f

Make the settings at the circulation pump when the temper-

ature differential between the flow and return temperature 

has stabilised.

 

f

Compare the resulting temperature differential between the 

flow and return at the appliance with the diagram “Maximum 

temperature differential on the heating side with buffer cyl-

inder”.

 

f

Set the buffer charging pump so that the maximum tempera-

ture differential is achieved or undershot.

 

f

If the appliance will be used for DHW heating, check the set-

ting of the pump head in DHW mode. 

 

f

If necessary, adjust the delivery head setting for the DHW 

primary pump.

 

f

Set the buffer charging pump and the DHW primary pump to 

∆p constant.

10.7  Condensate drain

A pipe for the condensate drain is fitted at the factory to the defrost 

pan. The pipe terminates near the aperture on the floor plate. The 

appliance is supplied with a two meter hose with elbow plug-in 

fittings for draining the condensate.

 

f

Secure the hose supplied on the pipe of the defrost pan.

10.8  External second heat generator

For dual mode systems, always connect the heat pump into the 

return of the second heat generator (e.g. oil boiler).

10.9  High limit safety cut-out for area heating 

system

!

 

Material losses

In order to prevent excessively high flow temperatures 

in the area heating system causing damage in the event 

of a fault, install a high limit safety cut-out to limit the 

system temperature.

Summary of Contents for WPL 47

Page 1: ...OPERATION AND INSTALLATION Air source heat pump WPL 47 WPL 57...

Page 2: ...0 Installation 10 10 1 Transport 10 10 2 Siting 10 10 3 Heating water connection 10 10 4 Oxygen diffusion 10 10 5 Filling the heating system 11 10 6 Minimum flow rate 11 10 7 Condensate drain 11 10 8...

Page 3: ...he second heat generator may flow through the heat pump Please note that the return water tempera ture may be a maximum of 60 C Maintenance work such as checking the electri cal safety must only be ca...

Page 4: ...ion is identified by the adjacent symbol f Read these texts carefully Symbol Meaning Material losses appliance damage consequential losses and environmen tal pollution Appliance disposal f This symbol...

Page 5: ...nal characteristics Suitable for underfloor and radiator heating systems Heat pump operates most efficiently on a low temperature heating system Still extracts heat from the outdoor air at 20 C outsid...

Page 6: ...d to the required temper ature The dual mode temperature is set too low Increase the dual mode temperature to e g 0 C The building is a new build and is in the screed drying phase Increase the dual mo...

Page 7: ...ernet Service Gateway ISG WPE heat pump extension Contact sensor Immersion sensor 9 Preparation 9 1 Sound emissions The appliance is louder on the air intake and air discharge sides than on the two en...

Page 8: ...nce is accessible from all sides f Provide a recess space in the base to enable supply lines to be routed into the appliance from below Note Allow the conduits for the supply lines to protrude slightl...

Page 9: ...tion and installation work in accordance with national and regional regulations WARNING Electrocution The connection to the power supply must be in the form of a permanent connection The appliance mus...

Page 10: ...h the water installation drawings that are part of the technical guide f Install a filling nozzle on site f Before connecting the heat pump flush the pipework thor oughly with suitable water Foreign b...

Page 11: ...supply Alternatively switch OFF the second heat generator f Operate the appliance in heating mode f In the menu SETTINGS HEATING STANDARD SETTING set parameter BUFFER OPERATION to ON The flow rate ca...

Page 12: ...contractor and in accordance with these instructions Permission to connect the appliance may need to be obtained from your local power supply utility 11 2 Terminal box WARNING Electrocution Before wor...

Page 13: ...fault The output passes the signal on to the external controller In the case of temporary faults the output switches the signal through for a specific time In the case of faults that result in a perm...

Page 14: ...ont and back panels into the mounting brackets of the hoods Simultaneously insert the tabs fixed to the bottom of the panels into the slots provided in the appliance frame f Secure the front and back...

Page 15: ...justment The efficiency of a heat pump decreases as the flow temperature rises The heating curve should therefore be adjusted with care Heating curves that are set too high cause the zone valves or th...

Page 16: ...hrough the emergency auxiliary heater If the emergency auxiliary heater cuts in this will result in higher running costs 14 2 1 Reduced night mode Note When reduced night mode is active this may resul...

Page 17: ...switched OFF and there is a risk of frost drain the system on the water side 17 Troubleshooting WARNING Electrocution Before removing the casing components disconnect all poles from the power supply N...

Page 18: ...g point If under these conditions precipitation occurs in the form of rain or fog ice may form on the air grille the fan blades or the airways If the fan comes into contact with this ice this creates...

Page 19: ...Installation Specification www stiebel eltron com WPL 47 WPL 57 19 19 Specification 19 1 Dimensions and connections g01 g02 i21 i21 D0000016788 g01 Air intake g02 Air discharge i21 Entry supply line...

Page 20: ...Motor overload relay F9 Fan fuse F10 Temperature limiter starting resistor K1 1 Safety contactor K1 Contactor resistance start K2 Compressor start contactor M1 Motor compressor M6 Fan motor M7 Electri...

Page 21: ...1 2 3 4 3 2 1 X62 3 2 1 6 5 4 3 2 1 3 2 1 7 6 5 4 3 2 1 5 4 3 2 1 3 2 1 p P3 3 2 1 p P1 B10 T B9 T B1 T N L PE M6 M 1 N L PE PE N L3 L2 L1 4 3 2 1 M1 M 3 5 3 1 2 4 6 K1 1 6 4 2 1 3 5 K1 5 3 1 2 4 6 K...

Page 22: ...High pressure switch F8 Motor overload relay F9 Fan fuse F10 Temperature limiter starting resistor K1 1 Safety contactor K1 Contactor resistance start K2 Compressor start contactor M1 Motor compresso...

Page 23: ...2 1 3 2 1 7 6 5 4 3 2 1 5 4 3 2 1 3 2 1 p P3 3 2 1 p P1 B10 T B9 T B1 T N L PE M6 M 1 N L PE PE N L3 L2 L1 4 3 2 1 M1 M 3 5 3 1 2 4 6 K1 1 6 4 2 1 3 5 K1 5 3 1 2 4 6 K2 T1 T2 T3 X3 X32 X37 5 4 3 2 1 M...

Page 24: ...0 1 2 3 84_03_01_0032_ Y Heating output kW X Inlet temperature of the WQA medium C 1 Flow temperature 35 C 2 Flow temperature 45 C 3 Flow temperature 55 C Power consumption 15 10 5 20 10 30 0 10 20 40...

Page 25: ...on com WPL 47 WPL 57 25 Coefficient of performance 1 2 3 4 5 6 20 10 30 0 10 20 40 1 2 3 84_03_01_0034 Y Coefficient of performance X Inlet temperature of the WQA medium C 1 Flow temperature 35 C 2 Fl...

Page 26: ...40 1 2 3 84_03_01_0035 Y Heating output kW X Inlet temperature of the WQA medium C 1 Flow temperature 35 C 2 Flow temperature 45 C 3 Flow temperature 55 C Power consumption 15 10 5 20 10 30 0 10 20 4...

Page 27: ...on com WPL 47 WPL 57 27 Coefficient of performance 1 2 3 4 5 6 20 10 30 0 10 20 40 1 2 3 84_03_01_0037 Y Coefficient of performance X Inlet temperature of the WQA medium C 1 Flow temperature 35 C 2 Fl...

Page 28: ...2 22 SCOP EN 14825 3 79 3 42 Sound emissions Sound power level EN 12102 dB A 69 69 Sound power level max reduced night mode dB A 67 Sound pressure level at 1 m distance in free field dB A 59 61 Sound...

Page 29: ...t aluminium fittings 8 0 10 0 8 0 10 0 Chloride mg l 30 30 Conductivity softening S cm 1000 1000 Conductivity desalination S cm 20 100 20 100 Oxygen 8 12 weeks after filling softening mg l 0 02 0 02 O...

Page 30: ...those subsidiaries Such guarantee is only grant ed if the subsidiary has issued its own terms of guarantee No other guarantee will be granted We shall not provide any guarantee for appliances acquire...

Page 31: ...www stiebel eltron com WPL 47 WPL 57 31 NOTES...

Page 32: ...rs B P 85107 57073 Metz C dex 3 Tel 0387 7438 88 Fax 0387 7468 26 info stiebel eltron fr www stiebel eltron fr Hungary STIEBEL ELTRON Kft Gy r u 2 2040 Buda rs Tel 01 250 6055 Fax 01 368 8097 info sti...

Reviews: