background image

INSTALLATION 

 

Shutdown

www.stiebel-eltron.com 

WPL ACS classic | 

17

The following steps will help you to adjust the heating curve cor-

rectly:

 

- Fully open thermostatic or zone valves in a lead room (e.g. 

living room and bathroom). 

We do not recommend installing thermostatic or zone valves 

in the lead room. Control the temperature for these rooms 

via remote control.

 

- At different outside temperatures (e.g. –10 °C and +10 °C), 

adjust the heating curve so that the required temperature is 

set in the lead room.

Standard values to begin with:

Parameters

Underfloor heating 

system

Radiator heating 

system

Heating curve

0.4

0.8

Controller dynamics

10

10

Comfort temperature

20 °C

20 °C

If the room temperature is not high enough in spring and autumn 

(approx. 10 °C outside temperature), go to the heat pump manager 

menu under "SETTINGS / HEATING / HEATING CIRCUIT" and raise 

the "COMFORT TEMPERATURE" parameter.

 

Note

If no remote control is installed, raising the "COMFORT 

TEMPERATURE" parameter leads to a parallel offset of 

the heating curve.

If the room temperature is not high enough when outside temper-

atures are low, increase the "HEATING CURVE" parameter.
If you raise the "HEATING CURVE" parameter, adjust the zone valve 

or thermostatic valve in the lead room to the required temperature 

when outside temperatures are high.

!

 

Material losses

Never reduce the temperature in the entire building by 

closing all zone or thermostatic valves, but by using the 

setback programs.

When everything has been implemented correctly, the system 

can be heated to its maximum operating temperature and vented 

once again.

!

 

Material losses

With underfloor heating systems, observe the maximum 

permissible temperature for the system.

12.3.2  Other settings

f

f

For operation with and without buffer cylinder, observe 

chapter "Operation / Menu structure / Menu SETTINGS / 

STANDARD SETTING / BUFFER OPERATION" in the operating 

and installation instructions of the WPM.

If using the heat-up program

If you use the heat-up program, make the following settings on 

the WPM:

f

f

Initially set the "DUAL MODE TEMP HZG" parameter to 30 °C.

f

f

Set the "LOWER APP LIMIT HZG" parameter to 30 °C.

 

Note

Following the heat-up process, return the "DUAL MODE 

TEMP HZG" and "LOWER APP LIMIT HZG" parameters to 

their default values or to the system values.

13.  Shutdown

!

 

Material losses

Never interrupt the heat pump power supply, even out-

side the heating season. Otherwise, system frost protec-

tion is not guaranteed. 

The heat pump manager automatically switches the heat 

pump to summer or winter mode. 

13.1  Standby mode

To shut down the appliance, simply set the heat pump manager 

to "Standby mode". This way the safety functions that protect the 

system remain enabled, e.g. frost protection.

13.2  Power interruption

If the system is to be isolated from the power supply permanently, 

please observe the following:

!

 

Material losses

f

f

If the heat pump and frost protection are completely 

switched off, drain the system on the water side.  

14.  Maintenance

!

 

Material losses

Keep the air discharge and intake apertures free from 

snow and ice.

f

f

Remove any leaves or other foreign bodies from the evapora-

tor fins periodically.

We recommend a regular inspection (to establish the current con-

dition of the system), and maintenance if required (to return the 

system to its original condition).

Summary of Contents for WPL 07 ACS classic

Page 1: ...OPERATION AND INSTALLATION Air water heat pump WPL 07 ACS classic WPL 09 ACS classic WPL 17 ACS classic ...

Page 2: ... Installation 11 10 1 Transport 11 10 2 Siting 11 10 3 Flow and return connection 12 10 4 Fitting the push fit connectors 12 10 5 Heating water connection 12 10 6 Oxygen diffusion 13 10 7 Filling the heating system 13 10 8 Minimum flow rate 13 10 9 Setting the flow rate on the heating side 13 10 10 External second heat source 14 10 11 High limit safety cut out for underfloor heating systems 14 11 ...

Page 3: ...s have discharged Never interrupt the heat pump power supply even outside the heating season Otherwise sys tem frost protection is not guaranteed If the heat pump and frost protection are completely switched off drain the system on the water side OPERATION 1 General information The chapters Special Information and Operation are intended for both the user and qualified contractors The chapter Insta...

Page 4: ... flow rates A confirmation of the specified output data can only be obtained if the test conducted for this purpose is also performed in ac cordance with the test conditions defined in the first paragraph of this section 2 Safety 2 1 Intended use The appliance is designed for room heating and cooling within the application limits given in the specification This appliance is intended for domestic u...

Page 5: ...ance via the free condensate drain and seeps away into the gravel bed Material losses In the defrost cycle the fan is switched off and the heat pump circuit is reversed The heat required for defrosting is drawn from the buffer cylinder For operation without a buffer cylinder observe chapter Operation Menu struc ture Menu SETTINGS STANDARD SETTING BUFFER OPERATION in the operating and installation ...

Page 6: ...uses reset the MCBs if required Notify your qualified contractor if the fuses MCBs blow trip again Condensate collects on the outside of the appliance and on the air grille The heat pump is extract ing heat from the outdoor air to heat the building This can cause the hu midity in the outdoor air to accumulate as dew or frost on the cooled heat pump casing This is not a defect The fan runs when the...

Page 7: ... 200 S classic or integral cylinder HSBC 200 S Without integral emergency booster heater Hydraulic module HMS Trend BE cylinder and hydrau lic module HSBB 200 S classic BE or integral cylinder HSBC 200 S BE 8 2 2 Further accessories Remote control for heating systems FEK Remote control for heating systems FE7 High limit safety cut out for underfloor heating systems STB FB 9 Preparations D000006016...

Page 8: ...e appliance is accessible from all sides 9 3 1 Condensate drain WARNING Injury At temperatures below freezing point ice may form f f Do not allow the gravel bed or surrounding area to slope downwards towards paths Material losses The foundations of the building must have a damp proof membrane Note f f Never use grit for the gravel bed Example Gravel bed under T support SK 2 800 100 300 a D00000634...

Page 9: ...0 865 WPL 17 ACS classic 1000 995 f f Lay a drainage pipe under the appliance to drain moisture away from the building f f Create a gravel bed below the condensate drain of the appliance 9 3 2 Siting Example T support SK 2 B A 1 3 2 150 150 D0000063486 1 Air intake side 2 Air discharge side 3 Main wind direction Heat pump A B WPL 07 ACS classic 865 500 WPL 09 ACS classic 865 500 WPL 17 ACS classic...

Page 10: ...s against humidity damage and UV radiation by means of a conduit f f Protect all pipe fixings and external wall ducts with anti vi bration insulation 9 5 WPM heat pump manager A WPM heat pump manager is required to operate the appliance This controls the entire heating system The heat pump manager is installed in the products defined as required accessories see chapter Installation Appliance descr...

Page 11: ...ugh a wall 2 5 mm for routing above the surface 1x B 16 A Control unit 1 5 mm The electrical data is provided in chapter Specification You re quire a J Y St 2x2x0 8 mm cable as a BUS cable Note The appliance includes an inverter for the variable speed compressor In case of a fault inverters can cause DC residual currents If RCDs are provided they have to be type B AC DC sensitive A DC residual cur...

Page 12: ...onnection The connector must be in its relaxed position before the pipe is inserted In this position there is a small gap between the screw cap and main body 26_03_01_0693 3 1 2 4 1 Retainer 2 Screw cap 3 Gap between screw cap and main body 4 Main body 26_03_01_0693 Pipe Ø 28 mm Depth of insertion A 44 mm Material losses Pipe ends must be deburred f f Always use a pipe cutter to trim pipes f f Pus...

Page 13: ...itives e g glycol to the fill water Note With a conductivity 1000 μS cm desalination treatment is recommended in order to prevent corrosion Note Suitable appliances for water softening as well as for filling and flushing heating systems can be obtained via trade suppliers 10 7 2 Filling the heating system f f Fill the heating system on the heating side 10 7 3 Venting the heating system The applian...

Page 14: ...sic 400 16 21 3x70 21 2x70 WPL 17 ACS classic 600 19 21 3x70 21 2x70 Buffer cylinder always required Recommended buffer cylinder volume underfloor heating system Recommended buffer cylinder volume radiators Activate the integral emergency booster heater WPL 07 ACS classic No 100 100 yes WPL 09 ACS classic No 100 100 yes WPL 17 ACS classic No 100 100 yes f f Install the open heating circuit s in th...

Page 15: ...ation Appliance description Accessories Appliance func tion Effect of the electric emergency booster heater Mono energetic operation If the dual mode point is undershot the electric emer gency booster heater safeguards both the heating opera tion and the delivery of high DHW temperatures Emergency mode Should the heat pump suffer a fault that prevents its con tinued operation the heating output wi...

Page 16: ...k with your local author ising body e g TÜV 12 1 Checks before commissioning Before commissioning check the following points note the com missioning checklist 12 1 1 Heating system Have you filled the heating system to the correct pressure and closed the automatic air vent valve 12 1 2 Temperature sensor Have you correctly positioned and connected the outside temperature sensor and return temperat...

Page 17: ...temperature and vented once again Material losses With underfloor heating systems observe the maximum permissible temperature for the system 12 3 2 Other settings f f For operation with and without buffer cylinder observe chapter Operation Menu structure Menu SETTINGS STANDARD SETTING BUFFER OPERATION in the operating and installation instructions of the WPM If using the heat up program If you use...

Page 18: ...ontrols on the IWS f f Read the following sections on troubleshooting and carry out the instructions 15 1 Checking the IWS DIP switch settings f f Carry out the following steps to make the IWS accessible D0000063487 f f Undo and remove the four screws on the sides of the hood f f Remove the hood D0000063488 f f Unscrew and remove the four screws on the top panel f f Remove the top panel D000006349...

Page 19: ...9 15 2 LEDs IWS BA D0000063997 1 2 1 Reset button 2 LEDs The following table shows the meaning of the LEDs on the IWS LED indicator Meaning Red LED flashes Single fault The appliance shuts down The appli ance restarts after 10 minutes The LED extinguish es Red LED illuminates Multiple faults occurred The appliance shuts down The appliance only restarts following a reset on the IWS The internal fau...

Page 20: ...ely from the appliance f f Check whether the design output and temperature are set correctly Ice formation is particularly pronounced when a high heating output is called for at moderate outside temperatures f f Carry out a manual defrost repeatedly if required until the fan runs free again Observe the information in the operating and installation instructions for the heat pump manager and the STA...

Page 21: ... 109 189 334 410 b01 d45 g01 g02 e02 e01 D0000057580 WPL 07 ACS classic WPL 09 ACS classic WPL 17 ACS classic a10 appliance Height mm 740 740 812 a20 appliance Width mm 1022 1022 1152 b01 Entry electrical cables d45 Condensate drain e01 Heating flow Diameter mm 22 22 22 e02 Heating return Diameter mm 22 22 22 g01 Air intake g02 Air discharge ...

Page 22: ...re sensor PT1000 B2 Heating return temperature sensor PT1000 B5 Hot gas temperature sensor PT1000 B6 Outdoor air temperature sensor PT1000 B7 Compressor intake temperature sensor PT1000 B8 Evaporator discharge temperature sensor PT1000 B9 Frost protection temperature sensor PT1000 B13 Defrost end temperature sensor PT1000 B16 Oil sump temperature sensor PT1000 E2 Oil sump heater F3 High pressure s...

Page 23: ...erausgangstemperatur GND Ölsumpf Ölsumpf GND X12 7 Heizungsvorlauf Heizungsvorlauf GND Abtauendefühler Abtauendefühler GND Frostschutz Frostschutz GND 1 2 3 4 5 6 1 2 1 2 3 4 5 6 7 X12 9 1 2 3 4 X12 8 1 2 3 4 5 X12 10 GND 5V A Modbus B Modbus 1 2 3 4 X12 11 M7 M M9 M 2bn 1wh p P1 2bn 1wh p P3 Z15 5 turns D0000061603 X12 6 5 pin IWS plug bypass valve X12 7 6 pin IWS plug temperature sensors X12 11 ...

Page 24: ...7 ACS classic with HM S Trend X2 X1 GND X26 X4 N L1 L2 L3 X3 N L1 X2 X4 X3 T N L Fernb 3 Fernb 1 T MK T Aussen T WW T Koll T KUE T WW T 2 WE T Puffer T L H WW Zirk 2 WE WW M Z M A MKP HKP KUE Solar 2 WE 2 WE EVU L Netz nc H L L N N N PE PE L1 L2 L3 L L PE L PE N 1 2 3 A D0000068365 1 Heat pump 2 Fuse box 3 HM S Trend A Power OFF contact ...

Page 25: ... L1 X2 X4 X3 T N L Fernb 3 Fernb Fernb 1 T A T MK T Puf T Puf T WW T WW T Koll T A T MK T Koll T KUE T WW T KUE T WW T 2 WE T 2 WE T L H L Zirk 2 WE WW N Zirk 2 WE WW PE Zirk 2 WE WW L KUE Solar N KUE Solar PE KUE Solar 2 WE 2 WE EVU Netz L nc H L L N N N PE PE L1 L2 L3 L L PE L PE N N L1 L2 L3 1 3 2 A D0000068366 1 Heat pump 2 Fuse box 3 HSBB 200 S classic HSBC 200 S A Power OFF contact ...

Page 26: ...ification 26 WPL ACS classic www stiebel eltron com 16 4 Application limit 16 4 1 Heating D0000068576 X Outside temperature C Y Flow temperature C 16 4 2 Cooling D0000068578 X Outside temperature C Y Flow temperature C ...

Page 27: ...c Heating output 0 5 10 20 15 10 5 0 5 10 15 20 1 2 3 4 5 6 D0000068470 X Outside temperature C Y Heating output kW 1 Max W55 2 Max W45 3 Max W35 4 Min W55 5 Min W45 6 Min W35 Cooling capacity 0 1 1 2 2 3 7 9 11 13 15 17 19 21 23 1 2 D0000068474 X Flow temperature C Y Cooling capacity kW 1 Max A35 2 Min A35 ...

Page 28: ...Heating output 0 5 10 20 15 10 5 0 5 10 15 20 1 2 3 4 5 6 D0000068471 X Outside temperature C Y Heating output kW 1 Max W55 2 Max W45 3 Max W35 4 Min W55 5 Min W45 6 Min W35 Cooling capacity 0 1 1 2 2 3 3 4 7 9 11 13 15 17 19 21 23 1 2 D0000068474 X Flow temperature C Y Cooling capacity kW 1 Max A35 2 Min A35 ...

Page 29: ...Heating output 0 5 10 20 15 10 5 0 5 10 15 20 1 2 3 4 5 6 D0000068473 X Outside temperature C Y Heating output kW 1 Max W55 2 Max W45 3 Max W35 4 Min W55 5 Min W45 6 Min W35 Cooling capacity 0 1 2 3 4 5 6 7 7 9 11 13 15 17 19 21 23 1 2 D0000068474 X Flow temperature C Y Cooling capacity kW 1 Max A35 2 Min A35 ...

Page 30: ... consumption at A 15 W35 EN 14511 kW 1 18 1 42 2 84 Coefficient of performance COP at A7 W35 EN 14511 4 54 4 54 4 76 COP at A2 W35 EN 14511 3 75 3 72 3 97 COP at A 7 W35 EN 14511 2 81 2 72 2 92 COP at A 15 W35 EN 14511 2 46 2 41 2 49 Cooling capacity at A35 W7 max 2 15 1 62 1 73 Cooling capacity at A35 W7 partial load 2 38 2 38 2 40 Cooling capacity at A35 W18 max 3 12 3 12 2 88 Cooling capacity a...

Page 31: ...5 B0 W35 and 5 k m h 0 4 0 4 0 8 Nominal heating system flow rate for A 7 W35 and 5 K m h 0 55 0 70 1 34 Min heating flow rate m h 0 4 0 4 0 6 Nominal internal heating pressure drop hPa 75 122 149 Flow rate on heat source side m h 1300 1300 2200 Permissible operating pressure heating circuit MPa 0 3 0 3 0 3 Guarantee The guarantee conditions of our German companies do not apply to appliances acqui...

Page 32: ...w stiebel eltron cz Finland STIEBEL ELTRON OY Kapinakuja 1 04600 Mäntsälä Tel 020 720 9988 info stiebel eltron fi www stiebel eltron fi France STIEBEL ELTRON SAS 7 9 rue des Selliers B P 85107 57073 Metz Cédex 3 Tel 0387 7438 88 Fax 0387 7468 26 info stiebel eltron fr www stiebel eltron fr Hungary STIEBEL ELTRON Kft Gyár u 2 2040 Budaörs Tel 01 250 6055 Fax 01 368 8097 info stiebel eltron hu www s...

Reviews: