STIEBEL ELTRON SOM 6 SI Installation And Troubleshooting Manual Download Page 14

SOM 6 SI

© 06184 som_6_si.monen.ind

d

|

 

14

4. Troubleshooting tips

can fuse T4A

If a malfunction occurs, a notification is given on the display 
of the controller:

Operating control lamp

Warning symbol

°F

Ω

°F

Ω

14

961

131

1213

23

980

140

1232

32

1000

149

1252

41

1019

158

1271

50

1039

167

1290

59

1058

176

1309

68

1078

185

1328

77

1097

194

1347

86

1117

203

1366

95

1136

212

1385

104

1155

221

1404

113

1175

230

1423

122

1194

239

1442

Resistance values of the 

Pt1000-sensors

1

2

S1

S2

S3

3

4

5

6

Temp. Sensor Pt1000

L

N

R1

N

20

19

18

17

14

13

12

2 (1) A 115 V~

T4A

US-West Hatfield, MA 01088

SOM 6 SI

Inc.

S4

7 8

Symptom

Possible Cause and Remedies List

Operating control lamp flashes red. The 

 

symbol is displayed and the 

 symbol is flashing. 

The indication channel of the relevent sensor 
displays 888.8 instead of the temperature.

SOM unit is sensing an open circuit condition.

Measure the resistance between the two terminals to which 

1. 

the relevent sensor is attached. If it measures infinite resis-
tance continue to step 2. If it measures a resistance within 
range of the above chart, call for service.
Disconnect the sensor wire from the terminals and measure 

2. 

the resistance between the two wires. If it still measures infi-
nite resistance continue to step 3. If it measures a resistance 
within range of the above chart, there is a problem with the 
connection from the sensor wire to the terminal.
This problem lies either with the sensor or the wire/connec-

3. 

tions. In order to determine whether the problem lies with 
the sensor itself, the sensor must be disconnected from any 
extension wire and its resistance must be measured. If, when 
the sensor is disconnected, the resistance is measured to be 
within the values of the resistance chart the problem is with 
the extension wire/connections.

Summary of Contents for SOM 6 SI

Page 1: ...SOM 6 SI Thanks for buying this product Read this manual carefully to get the best perfomance from this unit SOM 6 SI Installation Configuration andTroubleshooting Manual manual...

Page 2: ...ELTRON Inc Important notice Your own calculations and plans under consideration of the current norms and DIN directions should only be basis for your projects We don t offer a guarantee for the comple...

Page 3: ...ing control lamp Operation by 3 pushbuttons in the front of the housing Functions Temperature differential controller with optional add on system funtcions Function control according to BAW guidelines...

Page 4: ...s is 130 mm 4 Fasten the housing at its lower point 1 Installation Warning Switch off power supply before opening the housing 1 2 Electrical wiring The power supply to the controller must only be made...

Page 5: ...ard solar system with 1 store 1 pump and 3 sen sors The sensor S4 TRF can optionally be used for energy production measurement R1 S3 Symbol Specification S1 Collector sensor S2 Lower tank sensor S3 Up...

Page 6: ...r using keys 1 and or 2 The abbreviation for the parameter is displayed on the right side of the screen with the setting directly below and the set icon solid not blinking on the extreme right 2 Press...

Page 7: ...xchanger Sensor Collector with collector sensor Pump Store 1 with heat exchanger Temperature sensor 2 2 3 System screen only system screen Constantly green Normal operation Red green blinking Power up...

Page 8: ...ensor 3 Temperature 9 TRF Return Sensor Temperature 9 S4 Sensor 4 Temperature 9 h P x Operating Hours Counter 9 kWh Energy Production kWh 10 MWh Energy Production MWh 10 DT O x Switch On Temperature D...

Page 9: ...eratures if applicable Shows the current temperature of the sensor TRF return flow temperature TRF Return Flow Tempe rature Display range 40 482 F 3 1 5 Operating Hours Counter h P Number of hours whi...

Page 10: ...tion of the volume of heat exchanger fluid moved through the system and a comparison of the temperature of the fluid leaving the collector S1 with that of the fluid exiting the storage tank s heat exc...

Page 11: ...ector Emergency Shutdown Temperature If the collector emergency shutdown temperature EM is reached the solar pump R1 is deactivated in order to avoid damaging the solar components The default setting...

Page 12: ...This function will cool the tank back down to its maximum temperature when the collector temperature becomes low enough to facilitate such This prevents a cumulative overheating condition if the cool...

Page 13: ...nction is activated OCN Minimum Collector Temperature p 11 Off The T between DT O and DT F achieves the requisite effect for most situations OCF Antifreeze Option p 11 Off Unless the system is located...

Page 14: ...stead of the temperature SOM unit is sensing an open circuit condition Measure the resistance between the two terminals to which 1 the relevent sensor is attached If it measures infinite resis tance c...

Page 15: ...age is close to the nominal voltage of 120VAC continue to step 2 If the voltage is not correct the problem lies with the power supply to the unit Remove the unit s can fuse and measure its resistance...

Page 16: ...section 3 2 2 Make sure that all system components are properly insulated 3 Circulator pump is running collector is much hotter than store but the tank fails to heat up Make sure that the controller...

Reviews: