SOM 6 SI
3.2.1 Recommended Settings for Standard DHW System
Display
Code
Parameter Name
and Reference
Recommended Setting and Explanation
(All temperatures in
°
F)
DT O
Switch on Temperature
Difference (p. 10)
15°
Setting this too low can cause the circulator to cycle on and
off too frequently.
DT F
Switch off Temperature
Difference (p. 10)
5°
Too high of a
Δ
T between DT O and DT F can cause the
circulator to switch on and off too frequently.
S MX
Maximum Store
Temperature (p. 11)
140°
This will prevent the temperature at the top of the tank
from getting hot enough to cause the T & P valve to release.
This will also allow the cooling function to operate effectively.
EM
Collector Emergency
Shutdown Temperature
(p. 11)
310°
This prevents the HX fluid directly behind that in the
sensor well from causing the system to go into emergency
shutdown mode as soon as the cooling function is activated.
OCX
System Cooling
Function (p. 11)
On
Failure to change this option to ‘on’ will likely result in
overheating of the system at some point.
CMX
Maximum Collector
Temperature (p. 11)
230°
Having a relatively large
Δ
T between CMX and EM
prevents the HX fluid directly behind that in the sensor well
from causing the system to go into emergency shutdown mode
as soon as the cooling function is activated.
OCN
Minimum Collector
Temperature (p. 11)
Off
The
Δ
T between DT O and DT F achieves the requisite
effect for most situations.
OCF
Antifreeze Option
(p. 11)
Off
Unless the system is located in a region which rarely
experiences temperatures near freezing,
and
a very low glycol
to water percentage is being used.
OREC
Recooling Function
(p. 12)
On
This prevents a cumulative overheating of the system by
ensuring a relatively high
Δ
t between the tank temperature and
and the security switch-off of the tank (205
°
).
O TC
Tube Collector
Function (p. 12)
Off
Unless the system is utilizing tube collectors.
OHQM
Energy Production
Measurement (p. 10)
Off
Unless the installer has purchased an additional sensor and
wished to utilize this function.
HAND
Circulator Pump
Operating Mode (p. 12)
Auto
This is the normal operating mode. The other two
modes are for testing, charging, etc.
LANG
Language (p. 12)
En
(English)
For most applications in North America this is
appropriate, with some exceptions.
UNIT
Units for Temperature
Display (p. 12)
FAH
For most applications in North America this is
appropriate, but it is purely a matter of preference.
Please note that advanced users may desire to adjust certain parameters differently depending
on the circumstances. These suggested settings are merely a manner in which to configure the
unit that will avoid damage to the system from overheating. Installing the SOM 6 with the default
settings will likely result in an overheating condition of the solar system.