3.2.1 Recommended Settings for Standard DHW System

Display 

Code

Parameter Name 

and Reference

Recommended Setting and Explanation

(All temperatures in 

°

F)

DT O

Switch on Temperature 

Difference (p. 10)

15°

 Setting this too low can cause the circulator to cycle on and 

off too frequently.

DT F

Switch off Temperature 

Difference (p. 10)

 Too high of a 

Δ

T between DT O and DT F can cause the 

circulator to switch on and off too frequently.

S MX

Maximum Store 

Temperature (p. 11)

140° 

This will prevent the temperature at the top of the tank 

from getting hot enough to cause the T & P valve to release.  
This will also allow the cooling function to operate effectively. 

EM

Collector Emergency 

Shutdown Temperature

(p. 11)

310° 

This prevents the HX fluid directly behind that in the 

sensor well from causing the system to go into emergency 
shutdown mode as soon as the cooling function is activated.

OCX

System Cooling 
Function (p. 11)

On 

Failure to change this option to ‘on’ will likely result in 

overheating of the system at some point.

CMX

Maximum Collector 

Temperature (p. 11)

230°

 Having a relatively large 

Δ

T between CMX and EM 

prevents the HX fluid directly behind that in the sensor well 
from causing the system to go into emergency shutdown mode 
as soon as the cooling function is activated.

OCN

Minimum Collector 

Temperature (p. 11)

Off 

The 

Δ

T between DT O and DT F achieves the requisite 

effect for most situations.

OCF

Antifreeze Option

(p. 11)

Off 

Unless the system is located in a region which rarely 

experiences temperatures near freezing, 

and

 a very low glycol 

to water percentage is being used.

OREC

Recooling Function

(p. 12)

On 

This prevents a cumulative overheating of the system by 

ensuring a relatively high 

Δ

t between the tank temperature and 

and the security switch-off of the tank (205

°

).

O TC

Tube Collector 

Function (p. 12)

Off 

Unless the system is utilizing tube collectors.

OHQM

Energy Production 

Measurement (p. 10)

Off 

Unless the installer has purchased an additional sensor and 

wished to utilize this function.

HAND

Circulator Pump 

Operating Mode (p. 12)

Auto 

This is the normal operating mode.  The other two 

modes are for testing, charging, etc.

LANG

Language (p. 12)

En 

(English)

 

For most applications in North America this is 

appropriate, with some exceptions.

UNIT

Units for Temperature 

Display (p. 12)

FAH 

For most applications in North America this is 

appropriate, but it is purely a matter of preference.

Please note that advanced users may desire to adjust certain parameters differently depending 

on the circumstances. These suggested settings are merely a manner in which to configure the 

unit that will avoid damage to the system from overheating. Installing the SOM 6 with the default 

settings will likely result in an overheating condition of the solar system.

Summary of Contents for SOM 6 SI

Page 1: ...SOM 6 SI Thanks for buying this product Read this manual carefully to get the best perfomance from this unit SOM 6 SI Installation Configuration andTroubleshooting Manual manual...

Page 2: ...ELTRON Inc Important notice Your own calculations and plans under consideration of the current norms and DIN directions should only be basis for your projects We don t offer a guarantee for the comple...

Page 3: ...ing control lamp Operation by 3 pushbuttons in the front of the housing Functions Temperature differential controller with optional add on system funtcions Function control according to BAW guidelines...

Page 4: ...s is 130 mm 4 Fasten the housing at its lower point 1 Installation Warning Switch off power supply before opening the housing 1 2 Electrical wiring The power supply to the controller must only be made...

Page 5: ...ard solar system with 1 store 1 pump and 3 sen sors The sensor S4 TRF can optionally be used for energy production measurement R1 S3 Symbol Specification S1 Collector sensor S2 Lower tank sensor S3 Up...

Page 6: ...r using keys 1 and or 2 The abbreviation for the parameter is displayed on the right side of the screen with the setting directly below and the set icon solid not blinking on the extreme right 2 Press...

Page 7: ...xchanger Sensor Collector with collector sensor Pump Store 1 with heat exchanger Temperature sensor 2 2 3 System screen only system screen Constantly green Normal operation Red green blinking Power up...

Page 8: ...ensor 3 Temperature 9 TRF Return Sensor Temperature 9 S4 Sensor 4 Temperature 9 h P x Operating Hours Counter 9 kWh Energy Production kWh 10 MWh Energy Production MWh 10 DT O x Switch On Temperature D...

Page 9: ...eratures if applicable Shows the current temperature of the sensor TRF return flow temperature TRF Return Flow Tempe rature Display range 40 482 F 3 1 5 Operating Hours Counter h P Number of hours whi...

Page 10: ...tion of the volume of heat exchanger fluid moved through the system and a comparison of the temperature of the fluid leaving the collector S1 with that of the fluid exiting the storage tank s heat exc...

Page 11: ...ector Emergency Shutdown Temperature If the collector emergency shutdown temperature EM is reached the solar pump R1 is deactivated in order to avoid damaging the solar components The default setting...

Page 12: ...This function will cool the tank back down to its maximum temperature when the collector temperature becomes low enough to facilitate such This prevents a cumulative overheating condition if the cool...

Page 13: ...nction is activated OCN Minimum Collector Temperature p 11 Off The T between DT O and DT F achieves the requisite effect for most situations OCF Antifreeze Option p 11 Off Unless the system is located...

Page 14: ...stead of the temperature SOM unit is sensing an open circuit condition Measure the resistance between the two terminals to which 1 the relevent sensor is attached If it measures infinite resis tance c...

Page 15: ...age is close to the nominal voltage of 120VAC continue to step 2 If the voltage is not correct the problem lies with the power supply to the unit Remove the unit s can fuse and measure its resistance...

Page 16: ...section 3 2 2 Make sure that all system components are properly insulated 3 Circulator pump is running collector is much hotter than store but the tank fails to heat up Make sure that the controller...

Reviews: