www.stiebel-eltron-usa.com
Accelera® 220-300 E |
5
EN
GL
ISH
14˝
(0.4 m)
2´
(0.6 m)
8˝
(0.2 m)
6´
(1.8 m)
Air flow
intake
Air flow
intake
Air flow
exhaust
Air flow
exhaust
2´
(0.6 m)
Air flow
intake
Air flow
exhaust
6´
(1.8 m)
Minimum room volume:
800 ft
2
,
10´ x 10´ x 8´
(22.7 m
2
, 3 m x 3 m x 2.4 m)
Acceptable positioning, vent parallel to a wall:
Acceptable positioning, vent parallel to a wall in a corner:
2´
(0.6 m)
2´
(0.6 m)
8˝
(0.2 m)
8˝
(0.2 m)
6´
(1.8 m)
42˝ (220 E)
60˝ (300 E)
›
Do not install in a room
with less than 800 cubic
feet of total volume.
›
Do not install with the air
exhaust pointing at a wall
or any surface closer than
6 feet away.
›
Do not install with the air
intake pointing to a wall or
any surface closer than 2
feet away.
›
If you are installing an
Accelera 220 E next to
another appliance, the
appliance cannot be
taller than 42˝. If you are
installing an Accelera 300
E, the appliance cannot
be taller than 60˝. This
restriction is to prevent an
appliance from obstructing
air fl ow to and from the
Accelera.
›
Failure to follow
installation instructions
will void the factory
warranty.
QUICK START-UP GUIDE
Required room dimensions and clearances