DIL Switch Settings – Programmable Features
Important:
Changes made to any DIL switch settings will only take effect after the Alert Point
has been reset using the master key switch.
Factory settings
Features
SW1
SW2
SW3
Tone
Sound Pattern
OFF
OFF
OFF
1
800Hz - 970Hz (Sweep)
ON
OFF
OFF
2
800Hz - 970Hz (Sweep)
OFF
ON
OFF
3
988Hz / 250ms - 645Hz / 250ms (Alternating)
ON
ON
OFF
4
670Hz / 250ms - 845Hz / 370ms (Alternating)
OFF
OFF
ON
5
800Hz - 970Hz in 330ms (Sweep)
ON
OFF
ON
6
2400Hz - 2850Hz in 110ms (Sweep)
OFF
ON
ON
7
2400Hz - 2850Hz in 330ms (Sweep)
ON
ON
ON
8
Not Implemented
A ction
External Power Provided -
(12-30V DC)
External power is to be supplied. NB: absence of power will indicate
fault (LED flashing red )
No external power is to be supplied. NB: absence of power will not
indicate a fault
Relay is only triggered on the activated unit in a network
Integral Sounder Alarm
Tone
SW4 ON
SW4 OFF
SW5 ON
DI L S w itch S etting
Unit's Relay activates in a network even if this unit was not triggered
External Sounders/Beacons are NOT triggered during `alarm'
condition
External Sounders/Beacons are triggered during `alarm' condition
Relay Mode
Disable External Sounders
& Strobes / Beacons
SW5 OFF
SW6 ON
SW6 OFF
Sounder Duration Timer
SW7 SW8
OFF OFF
ON OFF
OFF ON
ON ON
Sounder Duration
Sounders run continuously (until manually reset)
Sounders switch off automatically after 30 seconds
Sounders switch off automatically after 3 minutes
Sounders switch off automatically after 20 minutes
Strobe / Beacon Duration
Timer
SW9 SW10
Strobe / Beacon Duration
OFF OFF
Strobes / Beacons run continuously (until manually reset)
ON OFF
Strobes / Beacons switch off automatically after 30 seconds
OFF ON
Strobes / Beacons switch off automatically after 3 minutes
ON ON
Strobes / Beacons switch off automatically after 20 minutes
Auto Reset
SW11 ON
SW11 OFF
Alert Point returns to `standby' condition after resetting with the
reset key
Alert Point latches in 'alarm' condition until it is manually reset using
the master key switch
The Alert Point expects to be connected to another Alert Point,
otherwise a fault is indicated (LED flashing / constant red)
No fault will be indicated if an Alert Point is not connected to
another Alert Point, it is not looking for a connection
Networking the Alert Point
SW12 ON
SW12 OFF