 Installing External 12-30 VDC Power Supply

Alarm Condition:  If the unit is activated in the event of an emergency (depression of  

the operating element) it will immediately emit an alarm tone for the duration selected, 

an activation flag will drop into view and the LED will flash red every 8 seconds until the 

unit is reset.

Resetting Unit: 

1.  DIL switch settings: changes will only take effect when the unit has been powered 

     back up using the master key switch.

2.  Silencing Alarm : If the operating element has been depressed the reset Key is to 

     be used to reset the unit, returning it to Standby Mode.  

 

 

Note:

 the master key switch can be used to silence the alarm but this will turn the unit ‘OFF’ 

and the alarm will continue to sound when the unit is turned back `ON’.

Power Loss: In the event of any loss of power, the LED will turn red and emit a short  

beep every 90 seconds. The unit will still run safely using the 9 VDC battery as a back 

up. As soon as power is restored the unit will automatically return to the `standby’  

condition.

Low or No Battery: If the unit is reset but the battery is at low power or not attached a 

fault will be indicated – the LED will turn red and the unit will emit a short single  

beep every 90 seconds.

 

The unit automatically checks for low battery status every 16 minutes, during  this 

period if the battery falls into low battery condition (or is disconnected in the presence 

of an external power source), the LED will turn red and emit a short beep every 90 

seconds upon detection at the end of any 16 minute cycle. The battery will either need 

replacing or reconnecting and the unit reset before it will return to a standby condition.

Step 1.

  Ensure that the unit is switched ‘OFF’. 

Step 2. 

 Insert the external power wires into the correct terminals.        

Step 3.

  Connect the 9 VDC battery. The battery must be fitted as it 

             will become a backup if there is a power failure.

Step 4.

  DIL switch SW4 – should be `ON’ (external power required).

Step 5.

  Turn the unit `ON’ using the master key switch.

Step 6.

  The LED will illuminate to a constant green indicating that the unit is functioning correctly.

External Power +

External Power -

Need technical support? Call us on +44 (0)1527 520 999

Summary of Contents for Alert Point

Page 1: ...Alert Point Installation Guide User Manual...

Page 2: ...cludes an integral sounder and resettable call point Manufactured from tough polycarbonate the Alert Point is designed for use in industrial as well as commercial or retail applications Quick and easy...

Page 3: ...Switch 3 Front Cover 2 Chassis Specifications Power source 9 VDC battery supplied or 12 30 VDC Standby current 45 A Alarm current 28mA low volume 32mA high volume Operating temperature 0 C to 49 C So...

Page 4: ...ts x4 Step 2 Attaching the chassis Attach by pushing the chassis over the 4 fixing clips on the mounting plate highlighted Fixing clip Step 3 Consult the User Manual for other programmable features Pr...

Page 5: ...y condition Step 6 Test A warning indicator drops into view the unit will alarm and the LED will turn red when the Alert point is activated Step 7 Reset the unit A quick turn of the key and the Alert...

Page 6: ...pips on the reset key provided push firmly into each of the 4 corner clips individually releasing them whilst at the same time gently pulling the cover away from the remainder of the unit Need techni...

Page 7: ...7 User Manual...

Page 8: ...after the selected time has elapsed The LED will continue to flash red until the unit is reset using the reset key 6 External Strobe Timer Options DIL Switch No SW9 SW10 4 strobe durations are availa...

Page 9: ...16 minute cycles If the battery falls below the recommended power level the unit will display a fault emitting a periodic single beep Battery life The working life of the 9 VDC battery under normal st...

Page 10: ...cally return to the standby condition Low or No Battery If the unit is reset but the battery is at low power or not attached a fault will be indicated the LED will turn red and the unit will emit a sh...

Page 11: ...nds or will remain constant if connected to an external power supply indicating that the unit is functioning correctly Step 6 Test When the operating element is depressed the unit will go into alarm c...

Page 12: ...rrectly Step 6 Test When the operating element is depressed the unit will go into alarm condition the externally installed strobe s beacon s should now flash Step 7 Reset the Alert Point using the res...

Page 13: ...used If the Zener diode is removed the Alert Point will trace a break in the loop and signal a fault The Zener diode must be installed at the end of line when linking detectors off the detector termi...

Page 14: ...ting into the network terminals ensure the Network In and the Network Out wires are switched over as shown below Step 5 Turn both units ON using the master key switch Step 6 Both LEDs will now flash g...

Page 15: ...nt unit Step 5 Important On the final unit e g Unit 3 ensure that the Network Out terminal is linked back to the Network In terminal on unit 1 creating a loop It is not necessary to do this step for t...

Page 16: ...e their Network In or COMMON connections they will both signal a fault Note to check that the network is functioning correctly whilst avoiding having to wait 90 seconds for verification turn the unit...

Page 17: ...ving any Check ext power lead connections switch OFF SW4 if no ext supply Reset key not resetting Alert Point when in alarm condition Auto reset option turned OFF DIL switch SW11 should be ON No sound...

Page 18: ...ive loop connection into the COM terminal The unit will independently sound during alarm condition as well as sending a trigger signal back the alarm panel It is recommended that all external detector...

Page 19: ...s Beacons are triggered during alarm condition Relay Mode Disable External Sounders Strobes Beacons SW5 OFF SW6 ON SW6 OFF Sounder Duration Timer SW7 SW8 OFF OFF ON OFF OFF ON ON ON Sounder Duration S...

Page 20: ...520 999 Fax 44 0 1527 501 999 Email info sti emea com Web www sti emea com USA Headquarters 2306 Airport Road Waterford Michigan 48327 Tel 248 673 9898 Fax 248 673 1246 Email info sti usa com Web www...

Reviews: