Wind and rain detector WRM/2 24V and Rain detector RM/2 24V
EIN
1
8
Jumper
1
4
2
3
1
2
3
4
5
6
S
STTO
OP
P
Connection and adjustment options
Connecting terminal:
Terminal
1.
Voltage 24 V DC
2.
Voltage supply -24 V DC
3.
Relay contact (operating contact)
4.
Relay contact (closing contact)
5.
Relay contact (opening contact) or wind sensor signal
6.
Wind sensor signal
Jumper
Jumper settings
Pins 2 and 3 bridged -> relay contact (opening contact) is positioned on Terminal 5.
Pins 1 and 4 bridged -> wind sensor operation (only for WRM/2)
Factory setting
Note:
For wind sensor operation DIP-Switch 7 must be switched to the ON position.
DIP-Switch
ON
1
8
DIP 1
Activation in windy conditions
For certain situations the wind detector can be switched off with DIP-Switch 1.
ON
Wind detector in operation. Activation in windy conditions.
OFF
Wind detector deactivated. No activation in windy conditions.
DIP-Switch
Relay contact
(opening contact)
Wind sensor
Control panel
1
2
3
4
5
6
S
STTO
OP
P
Control panel
Jumper
Wind sensor
Relay contact
1
4
2
3