5

Connections

Terminal 7: Output for trigger for 
pyrotechnic compressed gas generator (-) 
(onward transmission to the next DGM or 
termination circuit with diodes)
Terminal 8: Output for trigger for 
pyrotechnic compressed gas generator 
(+) (onward transmission to the next DGM 
or termination circuit with diodes)
Terminal 9: Monitoring circuit for DGM 
(onward transmission to the next DGM or 
termination circuit with diodes)

Control-& indicator panels

LED 

Colour: yellow
Function: malfunction*
LED lights up, in the event that:
- DG switch “DG off” is switched off
- fault occurs in the cable monitoring
- compressed gas generator is activated 
  after the trigger.
  
* Each malfunction message from the 
DGM compressed gas module is 
transmitted onwards to the respective 
assigned MM2x8A motor module. This 
malfunction is detected in the motor 
module as cable monitoring and is 
signalled as a fault.

LED 

Colour: red
Function: SHE trigger
The LED lights up, if a trigger has been 
activated.

LED 

ein/on

Colour: green
Function: actuator circuit is switched on 
“DG on”
LED lights up: DG switch in “DG on” 
position (compressed gas generator is 
live).

LED

 

aus/off

 

Colour: yellow
Function: actuator circuit is switched off
“DG off”
LED lights up: 
DG switch in “DG off” position
(compressed gas generator is secured).

Switch:

DG ON (1)
DG OFF (A)

Anschlüsse

Klemme 7: Ausgang Auslösung 
Pyrotechnische Druckgaserzeuger (-) 
(Weiterleitung zum nächsten DGM oder 
Abschluss Schaltung mit Dioden)
Klemme 8: Ausgang Auslösung 
Pyrotechnische Druckgaserzeuger (+) 
(Weiterleitung zum nächsten DGM oder 
Abschluss Schaltung mit Dioden)
Klemme 9: Überwachungsleitung DGM 
(Weiterleitung zum nächsten DGM oder 
Abschluss Schaltung mit Dioden)

Bedien- & Anzeigeelemente

LED

 

Farbe: Gelb.
Funktion: Störung*.
LED leuchtet, bei:
- DG-Schalter “DG aus” ist ausgeschaltet.
- Fehler in der Leitungsüberwachung.
- Druckgaserzeuger ist nach der 
  Auslösung ausgelöst.
  
* Jede Störungsmeldung vom Druckgas-
modul DGM wird an das jeweilige 
zugeordnete Motormodul MM2x8A 
weitergeleitet. Diese Störung wird im 
Motormodul als Leitungsüberwachung 
erkannt und als Fehler signalisiert.

LED

 

Farbe: Rot.
Funktion: RWA Auslösung.
Die LED leuchtet, wenn eine Auslösung
aktiviert wurde.

LED

 

ein/on

Farbe: Grün.
Funktion: Aktorkreis ist eingeschaltet, 
“DG an”.
LED leuchtet: DG-Schalter auf Position 
“DG an” (Druckgaserzeuger ist scharf).

LED

 

aus/off

Farbe: Gelb.
Funktion: Aktorkreis ist ausgeschaltet, 
“DG aus”.
LED leuchtet: DG-Schalter auf Position 
“DG aus” (Druckgaserzeuger ist 
gesichert).

Schalter

:

DG EIN (1)
DG AUS (A)

DGM

 

!

ein/on

aus/off

1

A

Schalter:

DG  EIN  (1)

DG  AUS  (A)

 

!

ein/on

aus/off

Switch:

DG  on  (1)

DG  off  (A)

Summary of Contents for MZ2 DGM

Page 1: ...compressed gas generator cascadable with further MZ2 DGM modules for connection of pressurized gas generators max 8 pieces with LED display to signal operating states and faults line monitoring of the connected pressurized gas generators snap on fitting onto 35 mm mounting rail Ausgabe 2 Gültig ab 07 10 2009 Datei Ti_MZ2_DGM_dt_engl indd Art Nr 24999654 Druckgasmodul MZ2 DGM Zum Anschluss von 24 V...

Page 2: ...power consumption Required mounting material is to be adapted to the frame and the corresponding load and is to be completed if necessary Any supplied mounting material is only part of the required amount Sicherheitshinweise Sicherheitshinweise die Sie unbedingt beachten müssen werden durch besondere Zeichen hervorgehoben Vorsicht Gefahr für Personen durch elektrischen Strom Achtung Nichtbeachtung...

Page 3: ...laration The equipment has been manufactured and tested according to the European regulations A corresponding manufacturer s declaration has been submitted You may only operate the system if a declaration of conformity exists for the entire system Sicherheitshinweise Leitungsverlegung und elektrischer Anschluss nur durch zugelassene Elektrofirma Die Kabelarten längen und querschnitte gemäß den tec...

Page 4: ... or not occupied max allowable 8 pieces clamp 3 clamp 2 clamp 1 Output motor module MM2x8A Klemmbelegung Die Nummerierung der Anschluss klemmen erfolgt bei allen MZ2 Modulen nach dem gleichen Prinzip Ausnahme Netzmodul NM16A Modul Draufsicht Begonnen wird links oben Jede Ebene tiefer wird die Nummerierung links beginnend fortgeführt Die Nummerierung der unteren Klemmreihe wird nach dem oben beschr...

Page 5: ... circuit is switched off DG off LED lights up DG switch in DG off position compressed gas generator is secured Switch DG ON 1 DG OFF A Anschlüsse Klemme 7 Ausgang Auslösung Pyrotechnische Druckgaserzeuger Weiterleitung zum nächsten DGM oder Abschluss Schaltung mit Dioden Klemme 8 Ausgang Auslösung Pyrotechnische Druckgaserzeuger Weiterleitung zum nächsten DGM oder Abschluss Schaltung mit Dioden Kl...

Page 6: ...stations and also in the assigned MZ2 group modules and MZ2 compressed gas modules Option DG ON DG OFF Switch DG ON 1 DG OFF A Bedien Anzeigeelemente Schiebeschalter DG Zum Ein und Ausschalten des Aktorkreises Funktion des Schiebeschalters Stellung 1 DG EIN bzw scharf Druck gasgenerator eingeschaltet und aktiv Stellung A DG AUS bzw Gesichert Druckgasgenerator ausgeschaltet und inaktiv z B für Wart...

Page 7: ...E operating stations and also in the assigned MZ2 group modules and MZ2 compressed gas modules the green LED display OK is extinguished in the SHE operating stations Die grüne LED OK in den RWA Bedienstellen leuchtet weiter Rauchabzug Lichtkuppeln schließen Nach erfolgter Auslösung muss der Schie beschalter im MZ2 Druckgasmodul in Stellung gesichert geschaltet werden Die gelbe LED Anzeige aus off ...

Page 8: ... extinguished Only now is the yellow LED display Malfunction extinguished and the green LED display OK lights up in the MZ2 motor module Functions for MZ2 Zurücksetzen der RWA Auslösung und der automatischen Melder Automatische Melder von Rauch befreien durch Ausblasen bzw bei starker Verschmutzung ersetzen Rauchabzug Lichtkuppeln schließen Nach erfolgter Auslösung muss der Schiebeschalter in der ...

Page 9: ...rator Anschlussmöglichkeiten Überwachungsdioden ein Druckgasmodul DGM mehrere Druckgasmodule DGM Diodenpolung Druckgasgenerator Druckgasgenerator max 8 Druckgasgeneratoren pro Linie Druckgasgenerator Überwachungsdioden Überwachungsdioden bei Kaskadierung mehrerer DG Module Überwachungsdioden im letzten Modul einsetzen Motorkreis A Motorkreis B Überwachung Ausg Auf Überwachung Ausg Auf Ausgang Akto...

Page 10: ...er Steuerung DG Dieses ist ein Ausführungsvorschlag Die jeweilige Landesbauordnung ist zu beachten d h evtl können mehrere RWA Bedienstellen und autom Melder gefordert werden Vor der Montage Installation und vor jeder Änderung den Schiebeschalter auf gesichert schalten Vor dem Anklemmen der Druckgasgeneratorenleitungen werden diese mittels Ohmmeter auf Durchgang gemessen Der Innenwiderstand sollte...

Page 11: ...rator zur Verwendung kommen 2 Die Klemmstellen in der Steuerzentrale sind für maximale Leitungsquerschnitte bis 2 5 mm ausgelegt Werden größere Querschnitte verwendet so ist eine Querschnitt reduzierung unmittelbar vor der Steuerzentrale durchzuführen Es sind die gültigen Vorgaben bzgl einer Verkabelung mit Funktionserhalt 30 Min oder 90 Min einzuhalten Abweichungen hierzu sind in jedem Fall mit d...

Page 12: ...ply 230 V AC Connection diagramm see page 10 Montagevariante Dieses ist ein Ausführungsvorschlag Die jeweilige Landesbauordnung ist zu beachten d h evtl können mehrere RWA Bedienstellen und autom Melder gefordert werden Rohrleitung Stahl 6 x 0 7 mm von NRWG Auslöseeinrichtung zum Pneumatikzylinder pneumatischer Hubzylinder Rauchabzugsklappe Lichtkuppel NRWG Auslöseeinrichtung Druckgasgenerator mit...

Page 13: ... and 9 Check whether the DG slider switch is switched to active If none of the above helps replace the module Blinkcodes der DGM Erkannte Fehler werden als Blinkfolge über die gelben Störungs LED s ausgegeben Die Blinkfolgen haben folgende Bedeutung Blinkfolge Fehler Auslöser DAUER Aktorüberwachung Leitungen fehlerhaft DAUER DG Schalter DG Schiebeschalter steht auf Position gesichert Aus kein Fehl...

Page 14: ... dry Material Housing plastic Colours light grey Halogen free nein Silicon free nein RoHS compliant nein Technische Daten Die Energieversorgungen und elektrischen Steuereinrichtungen sind ausschließlich mit den vom Hersteller zugelassenen Komponenten zu betreiben Elektrische Eigenschaften Stromaufnahme des Moduls 10 mA bei 27 5 V Betriebsspannung Leistungsaufnahme 0 28 VA bei 27 5 V Betriebsspannu...

Page 15: ...f a crossed out waste bin and the chemical symbol Cd Hg or Pb for the heavy metal that determines the classification of the hazardous substances contained Technische Daten In Abhängigkeit der verwendeten Zentralen ist bei der Dimensionierung der Energieversorgung und zur Dimensionierung der Kabelquerschnitte der Motorzuleitungen mit erhöhten Strömen im Anlaufmoment zu rechnen Ein funktionssicherer...

Reviews: