Betätigungsradien
Actuating radii
Rayons d'actionnement
Raggi di azionamento
Angulos de atuação
Радиусы привода в действие
AZ 335/355-B1, -B1-2245:
x = 52,7 mm, a min. 900 mm
AZ 335/355-B5:
x = 15,4 mm, a min. 900 mm
AZ 335/355-B5-Flex
x = 30,3 mm, a min. 100 mm
AZ 335/355-B6:
x = 13 mm, a min. 100 mm
AZ 335/355-B6-Flex
x = 28 mm, a min. 100 mm
AZ 335/355-B1, -B1-2245:
x = 52,7 mm, b min. 700 mm
AZ 335/355-B5:
x = 15,4 mm, b min. 700 mm
AZ 335/355-B5-Flex
x = 30,3 mm, b min. 100 mm
AZ 335/355-B6:
x = 13 mm, b min. 100 mm
deutsch (Originalsprache)
Technische Daten
Vorschriften
EN 60947-5-1; EN ISO 13849-1; EN ISO 14119
Gehäuse
Aluminium-Druckguss, pulverbeschichtet
festgelegtes Objekt
Betätige, nichtrostender Stahl 1.4301
Schaltertyp
Bauart 2
Kodierungsstufe
geringe Kodierung
Schaltglieder
Wechsler, 2 Öffner/1 Schließer, 1 Öffner/2
Schließer oder 2 Öffner mit Doppelunter-
brechung Zb, Öffner zwangsöffnend
A
Schaltsystem
Schleichschaltung
Schutzart
IP 67 nach IEC/EN 60529
Anschluss
Schraubanschlussklemmen, 2 Kontakte: max.
2,5 mm2 , 3 Kontakte: max. 1,5 mm2 (einschl.
Aderendhülsen)
Leitungseinführung
M20 x 1,5
B10d (10% Nennlast)
2 Millionen
TM
max. 20 Jahre
Uimp
4 kV
Ui
400 V
Ithe
2 Kontakte: 6 A; 3 Kontakte: 1,5 A
Gebrauchskategorie
AC-15; DC 13
English
Technical data
Standards
EN 60947-5-1; EN ISO 13849-1; EN ISO 14119
Enclosure
aluminium diecast, powder-coated
Defined object
actuator, sainless steel 1.4301
Switch type
type 2
Coding level
low coding
Switching elements
change-over, 2 NC/1 NO, 1 NC/2 NO or 2 NC
contacts contact with double break type Zb,
positive break NC contacts
A
Switching system
slow action
Degree of protection
IP 67 per IEC/EN 60529
Connection
screw connection terminals, 2 contacts: max.
2.5 mm
2,
3 contacts: max. 1.5 mm
2
(incl. con-
ductor ferrules)
Cable entry
M20 x 1.5
B10d (10% nominal
load)
2 millions
TM
max. 20 years
Uimp
4 kV
Ui
400 V
Ithe
2 contacts: 6 A; 3 contacts: 1.5 A
Utilisation category
AC-15; DC 13
Rated operating
current/voltage
2 contacts: 6 A/250 VAC; 0.25 A/230 VDC
3 contacts: 1.5 A/230 VAC; 0.27 A/250 VDC
Short-circuit protection
2 contacts: 6 A gG/gN fuse;
3 contacts: 1.5 A gG/gN fuse
Switching frequency
1800/h
Positive break travel
8.3 mm
Mechan. life
1 million operations
Ambient
temperature
-20 °C to +80 °C
x
a
x
b
Bemessungsbetriebs-
strom/-spannung
2 Kontakte: 6 A/250 VAC; 0,25 A/230 VDC
3 Kontakte: 1,5 A/230 VAC; 0,27 A/250 VDC
Kurzschlussschutz
2 Kontakte: 6 A gG/gN-Sicherung;
3 Kontakte: 1,5 A gG/gN-Sicherung
Schalthäufigkeit
1800/h
Zwangsöffnungsweg
8,3 mm
Mechan. Lebensdauer
1 Million Schaltspiele
Umgebungstemperatur
-20 °C bis +80 °C