O

PERATION

 

NOTE:    ENSURE  THAT  EMITTER  IS  INSTALLED BEFORE 
POWER  IS  APPLIED.    INSTALLING  EMITTER  AFTER 
POWER  HAS  BEEN  APPLIED  MAY 

TRIGGER  THE  “END

-

OF-LAMP-

LIFE  CIRCUIT”  AND

  THE  EMITTER  MAY  FAIL 

TO LIGHT.  IF THIS HAPPENS, SHUT OFF POWER FOR 10 

SECONDS AND THEN TURN POWER BACK ON.  EMITTER 
WILL THEN LIGHT. 

1.

 

Consult all applicable codes before installing. 
Check  fixture  label(s)  for  the  correct  power 
requirements  and  supply  the  correct  voltage 
from a suitable, protected (fused), and grounded 
power source. 

2. 

Air  Handler  should  have  signs  (provided  in 
English  and  Spanish)  in  appropriate  languages 
alerting  maintenance  personnel  to  the  possible 
hazard  of  looking  at  or  exposing  skin  to  UVC 
energy. Service accesses may be equipped with 
a  glass  or  Lexan

® 

window  to  view  Emitters; 

viewports  are  available  as  an  accessory.    UVC 
energy  does  not  penetrate  common  glass  or 
Lexan

®

.

 

3.  If applicable, remove outer cover of air handler.  

4.

 

UVC  energy  may  damage  some  plastics.  Wrap 
suspect  items  with  aluminum  tape;  use  metallic 
conduit or use other appropriate shielding where 
these items may be in "line of sight" of the UVC 
energy. 

5.

 

The  Emitter  shall  be  installed  downstream  from 
the  cooling  coil  and  above  the  drain  pan.    To 
achieve  equal  distribution  of  UVC  intensity  on 
the  face  of  the  coil,  the  Emitters  shall  be 
positioned from the face of the coil at a distance 
equal  to  half  the  vertical  height  that  the  light  is 
covering.  
 

6.  The Emitter shall also:

 

o

   

Be at least 1” away from any heating coil.  

o

   Not  make  contact  with  the  air  handler 

blower. 

7.  If  applicable,  replace  the  outer  cover  of  air 

handler.  

8.  Remove cover to ESE Fixture. 

 

 

9.  Using  the  fixture  base  as  a  template  scribe  and 

then create an insertion hole, 

2” diameter where 

you want the emitter to be located. 
 

CAUTION:  Do  not  drill  into  coil,  refrigerant  lines 
or other mechanical equipment.

 

 

10.  Install  support  bracket (item  4)  using  the  4  nuts 

4-40  provided  (item  5).    Align  the  face  of  the 
support bracket so that it faces the coiling coil on 
final installation.  The bracket can be rotated 360 
degrees at 90 degrees intervals. 

 

 

 

 

11.

 

Drill  suitable  holes  for  each  fastener  (unless 
using self-tapping screws). Using the proper #10 
fastener for your application, install fixture(s) and 
wire in accordance with the applicable code. 

12.

 

Install  UVC  Emitter.  Secure  with  spring  clip.  
Ensure  that  there  is  an  O-ring  on  the  emitter.  
Failure to install O-ring can possibly damage the 
emitter base. 

13.

  Complete  all  power  connections  and  replace 

cover to the fixture

 

14.

  Reconnect  power  to  the  air  conditioner  and 

toggle  the  installed  switch 

to  the  “On”  position.  

The  Emitter  should  emit  a  bright  blue  hue, 
indicating that it is properly powered.

 

15.

  Attach  the  Caution  Label  and  Lamp  Change 

Date  Label  to  air  handler  access  panel  so  they 
are clearly visible.

 

16.

  Emitters  need  to  be  periodically  replaced  to 

maintain  design  output.    Emitters  should  be 
replaced after 9,000 hours of use.

 

 

 

Summary of Contents for ESE 1 Series

Page 1: ...er may result Oil from fingerprints will permanently etch glass of Emitter and weaken structure If necessary clean Emitter using a Steril Aire cleaning kit isopropyl alcohol and a lint free wipe may be substituted UVC Emitters are fragile To prevent accidental breakage handle the UVC Emitter with care Voltages outside of the range designed for the unit will void the warranty and do permanent damag...

Page 2: ...stance equal to half the vertical height that the light is covering 6 The Emitter shall also o Be at least 1 away from any heating coil o Not make contact with the air handler blower 7 If applicable replace the outer cover of air handler 8 Remove cover to ESE Fixture 9 Using the fixture base as a template scribe and then create an insertion hole 2 diameter where you want the emitter to be located ...

Page 3: ...components interlock door switches relays motion detectors etc Emitter reaching end of life Replace with new Emitter Reset Power Defective Power supply Replace Power Supply Visibly Weak Emitter Light Bad Wiring Check wiring to emitter Emitter reaching end of life Replace Emitter Emitter too Cold If emitter is at or below 35 F 1 C Emitter is too cold to operate properly Red Orange Emitter Emitter r...

Page 4: ... been investigated by UL 2017 Steril Aire Inc All rights reserved 1391 REPLACEMENT PARTS PART NUMBER EGTS 24 VO Enhanced 24 Single Ended Emitter 21000310 EGTS 30 VO Enhanced 30 Single Ended Emitter 21000410 EGTS 36 VO Enhanced 36 Single Ended Emitter 21000510 EGTS 42 VO Enhanced 42 Single Ended Emitter 21000610 EGTS 50 VO Enhanced 50 Single Ended Emitter 21000910 EGTS 61 VO Enhanced 61 Single Ende...

Reviews: