GENERATOR 
UNDER 
VOLTAGE 

The generator output voltage has fallen below the pre-set pre-alarm 
setting after the 

Safety On 

timer has expired. 

 

GENERATOR OVER 
VOLTAGE 

The generator output voltage has risen above the pre-set pre-alarm 
setting. 

 

GENERATOR 
UNDER 
FREQUENCY 

The generator output frequency has fallen below the pre-set pre-
alarm setting after the 

Safety On 

timer has expired. 

 

GENERATOR OVER 
FREQUENCY 

The generator output frequency has risen above the pre-set pre-
alarm setting. 

 

 

EMERGENCY STOP 

The emergency stop button has been depressed. This is a failsafe 
(normally closed to battery positive) input and will immediately stop 
the set should the signal be removed. 
Removal of the battery positive supply from the emergency stop 
input will also remove DC supply from the Fuel and Start outputs of 
the controller. 

 

 

INTERNAL MEMORY 
ERROR 

The configuration file is corrupted. Contact your supplier for 
assistance. 

 
6.10 Fault finding 3110 

Unit is inoperative 
Read/Write 
configuration does not 
operate 

Check the battery and wiring to the unit.  
Check the DC supply.  
Check the DC fuse. 

Unit shuts down 

Check DC supply voltage is not above 16 Volts or below 9 Volts 
Check the operating temperature is not above 70°C.  
Check the DC fuse. 

Unit locks out on 
Emergency Stop 

Check emergency stop switch is functioning correctly.  
Check wiring is not open circuit. 

Low oil Pressure fault 
operates 
after engine has fired 

Check engine oil pressure.  
Check oil pressure switch/sensor and wiring, switch is Normally closed and 
opens with pressure. 

High engine 
temperature fault 
operates after engine 
has fired. 

Check engine temperature.  
Check switch/sensor and wiring.  
Check switch polarity is correct Normally open or Normally closed. 

Shutdown fault 
operates 

Check relevant switch and wiring of fault indicated on LCD display.  
Check configuration of input. 

Warning fault operates 

Check relevant switch and wiring of fault indicated on LCD display.  
Check configuration of input. 

Fail to Start is activated 
after pre-set number of 
attempts to start 

Check wiring of fuel solenoid.  
Check fuel lift pump operational & fuel supply to engine. 
Check battery supply.  
Check battery supply is present on the Fuel output of the module.  

Continuous starting of 
generator when in 

AUTO

 

Check that there is no signal present on the “Remote Start” input.  
Check configured polarity is correct. 

Generator fails to start 
on receipt of Remote 
Start signal. 

Check Start Delay timer has timed out. (Not configured on standard builds) 
Check signal is on “Remote Start” input.  
Confirm correct configuration of input is configured to be used as “Remote 
Start”. 
Check that the oil pressure switch or sensor is indicating low oil pressure to 
the controller. The set will not start if oil pressure is not low. 
 

Pre-heat inoperative 

Check wiring to engine heater plugs. Check battery supply. Check battery 
supply is present on the Pre-heat output of module.  

Summary of Contents for SSD10000

Page 1: ...0 1933 677916 E mail info stephill generators co uk Web www stephill generators co uk DO NOT OPERATE THE GENERATOR BEFORE READING THIS MANUAL AND ENGINE MANUFACTURER S OWNER S MANUAL AND WARNINGS THIS...

Page 2: ...Start checks 4 5 2 Warning 4 5 3 Control panel 4 5 4 Long term storage 4 6 0 DEEP SEA 3110 OPERATING INSTRUCTIONS 5 6 1 Description of controls 5 6 2 Starting the engine 5 6 3 Starting sequence 5 6 4...

Page 3: ...th Height Length Width Height Length Width Height Dimensions Skid 1285 655 900 1285 655 900 1285 655 900 Dimensions Trolley 1750 900 1080 1750 900 1080 1750 900 1080 Dimensions Road Trailer 2360 1300...

Page 4: ...generator while the engine is running Check the rating and electrical safety of the load before connecting the generator Equipment should never be connected that in total exceeds the specified rating...

Page 5: ...m exposure Used oil should not be allowed to contact the skin If this does occur wash off quickly with a proprietary hand cleanser 4 4 Safe Lifting Where mechanical assistance is used in lifting machi...

Page 6: ...ssure and high water temperature If engine runs out of fuel do not attempt to start until fuel bowl is full of diesel this can be achieved by pressing Fuel Pump Prime button until bowl is full of dies...

Page 7: ...rom the main alternator output frequency After the starter motor has disengaged the Safety On timer activates 10 Sec allowing Oil Pressure High Engine Temperature Under speed Charge Fail and any delay...

Page 8: ...iary inputs can be user configured and will display the message as written by the user FAIL TO START The engine has not fired after the pre set number of start attempts FAIL TO STOP The module has det...

Page 9: ...is not open circuit Low oil Pressure fault operates after engine has fired Check engine oil pressure Check oil pressure switch sensor and wiring switch is Normally closed and opens with pressure High...

Page 10: ...eaplc com 6 11 Fault finding general High engine temperature Check Water Antifreeze level in the radiator Check for loose wires on the temperature switch DC loom connector block Check the continuity o...

Page 11: ...terminals plug and socket Check VE supply Check VE on Glow plug trace back to battery via relay Check VE on Glow plug trace back to module via relay plug socket Starter Motor not operating Check Emer...

Page 12: ...004 015 0004 Fuel filter 015 0005 015 0005 In line fuel filter 015 0030 015 0030 Air filter 015 0003 015 0003 Fan belt 015 0007 015 0007 9 General spares Part Number Description Qty 015 0001 Kubota D7...

Page 13: ...3 SSD10000 Door spacer 8 9 1 Control panel spares Part Number Description Qty 045 0061 DEEP SEA 3110 1 036 0018 40A Circuit breaker 1 036 0028 40Amp RCD 30mA 1 036 0049 16A Re set 2 036 0052 32A Re se...

Page 14: ...air or use of parts not supplied by STEPHILL GENERATORS LTD Lack of or incorrect maintenance Fair wear and tear misuse negligence accidental damage improper storage and incorrect starting warm up run...

Page 15: ...mm black 1 x 6mm black 11 16 115v 16a socket 1 5mm Blue E N 1 5mm Brown L 4 0mm Blue 4 0mm Blue 115v 32a socket 115v 32a socket E N L E L N 4 0mm Brown 4 0mm Brown 40A RCD 11 16 2 5 8B 4B 7 8A 3 4A 6B...

Page 16: ...5mm 2 5mm 6mm 26 R3 32 19 1 31 5 20 23 R2 4 19 29 R1 5 29 29 25mm 25 SWITCH 40A 60A 19 23 25 25 6mm 4mm 2 5mm 1 STARTER MOTOR 25mm 20 26 GLOW PLUG 25 CHARGE ALTERNATOR 6mm 25 7 3 CHARGE ALTERNATOR OIL...

Page 17: ...ide 1 11 024 0150 SSD10000 PE32 NPE31 Alternator cowl 2 11 024 0181 SSD10000 PE28 Alternator cowl 2 12 024 0126 SSD10000 Battery bracket 1 13 024 0104 SSD10000 Battery tray 1 14 024 0154 SSD10000 Fuel...

Page 18: ...0127 Lifting eye 1 8 048 0008 Fuel cap 1 9 024 0113 Radiator flap 1 10 023 1029 Hinge 2 11 023 1019 Cam 28mm 1 12 023 1020 Insert slot 1 13 023 1021 Housing 1 R Golding D 21 09 10 Drawing updated Date...

Reviews: