3.5 Reference Barometric Pressure
The standard reference condition for total barometric pressure is 1 bar.
This corresponds to an altitude of approximately 100m. Above 100m the rated power
must be reduced.
3.6 Flammable Environment
Stephill generators must not be used in a flammable environment.
3.7 Saline Environment
Operation of the machine in a saline environment will require additional corrosion
protection.
4 Safety Considerations
4.1 General
All Stephill Generators comply with all the current EEC directives including:
2006/42/EC Machinery Directive
2000/14/EC Noise Emission in the Environment by Equipment for use outdoors
2004/108/EC EMC Directive
2006/95/EC Low Voltage Directive
4.2 Fuel
Fuels and lubricants are a potential source of fire. Lubricants in particular used engine oil,
are potentially carcinogenic. Direct contact should always be avoided by wearing suitable
rubber gloves when handling them. Be careful not to spill fuel, clean up any spillages.
Inhalation or swallowing of diesel should be avoided. If in doubt seek medical advice. All
other forms of contact are irritant and therefore should also be avoided. If skin contact is
made wash with soap and water.
4.3 Lubricating Oil
New oil presents no hazard following short term exposure.
Used oil should not be allowed to contact the skin. If this does occur, wash off quickly
with a proprietary hand cleanser.
4.4 Safe Lifting
Where mechanical assistance is used in lifting machines, ensure the lifting eye is used,
and that all components used to lift the machine are within their Safe Working Load
(SWL).
The integral lifting beam and associated lifting eye on the generator should be regularly
checked for signs of damage or gross corrosion.
All nuts and bolts associated with the lifting beam should be regularly checked for
tightness and corrosion.
Lifting equipment should not be attached directly to the engine/alternator except for lifting
of engine/alternator only.
4.5 Earth connection
All Stephill products are fitted with an earth stud on the control panel this must be
connected to an earthing system or spike. Any earth spike required is dependant on the
local conditions of use. The size is determined by reference to current IEE regulations or
to a competent electrician.
4.6 Fumes
Make sure that the generator is at least 2 metres away from any building during
operation. Operate in a well ventilated unconfined area, so that fumes can be properly
dispersed.
Silencer outlet should be facing an open area to prevent fumes being recirculated. There
is the danger of asphyxiation due to exhaust gases. Inhalation of poisonous exhaust
fumes can lead to serious injury or death. The generator must not be used in a poorly
ventilated or enclosed area.