INSSTCP15MA0116
18
lights up and the display indicates the temperature. In
this case, press down once again the Test button to
reinitialize the EGFPD, the red indicator turns off.
b) Failed test: The red indicator of the thermostat lights up
and the display indicates E4. In this case, disconnect the
heating system at the electrical panel and call Stelpro’s
customer service.
c) Failed test: The red indicator of the thermostat lights
up and the display shows only the time. In this case,
disconnect the heating system at the electrical panel and
contact Stelpro’s customer service. The thermostat has
detected a ground-fault.
security mode
This mode imposes a maximum temperature set point which
is impossible to exceed regardless of the mode in progress.
However, it is still possible to lower the set point at your
discretion. The programming of the Auto and Pre-Prog modes
also respects this maximum temperature set point. Please note
that when the Security mode is activated, it is impossible to
switch from the
mode to the
mode, and conversely.
Procedures to activate Security mode
1. Exit any adjustment mode to manually adjust the set point at
the desired maximum value.
2. Simultaneously press down the + and - buttons during
10 seconds (note that after 3 seconds, the icon starts
to blink and the software version and date are displayed.
Continue to press down these buttons).
3. After 10 seconds, the icon is displayed indicating that the
Security mode is activated. Then, release the buttons.
Procedures to deactivate Security mode
1. To deactivate the Security mode, cut off the power supply
of the thermostat at the electrical panel and wait at least
30 seconds.