- 17 -
DIP 6 / 7 / 8
Trigger mode
The trigger mode enables the user to choose which sensing technologies
should be used to initially turn the load on and which technologies are
required to keep it on. The following settings are possible:
DT Quattro COM1-24 / COM2-24 / DIM-24
Both:
Requires movement recognition by PIR and US
Either: Requires movement recognition by PIR or US
PIR:
Requires movement recognition by PIR
US:
Requires movement recognition by US
Inital occupancy:
Sensor technology used to turn the load on (PIR, US, Both, Either)
Maintain Occupancy:
Sensor technology used to keep the load on after initial occupancy (PIR, US, Both, Either)
The trigger mode is selected by DIP switches 6, 7 & 8.
on
1 2 3 4 5 6 7 8
TEST
MODE
MANUAL
ON / OFF
CONST.
OFF
NORMAL
MODE
AUTO
ON
CONST.
ON
TRIGGER MODE
Trigger mode options
n
Initial Occupancy
Maintain Occupancy
DIP
6
DIP
7
DIP
8
Option 1
Both
Either
OFF
OFF
OFF
Option 2
Both
Both
OFF
OFF
ON
Option 3
PIR
Either
OFF
ON
OFF
Option 4
US
Either
OFF
ON
ON
Option 5 (factory setting)
Either
Either
ON
OFF
OFF
Option 6
US
US
ON
OFF
ON
Option 7
PIR
PIR
ON
ON
OFF
Option 8
Either
Both
ON
ON
ON