True Presence BT IPD detection setting
The range can be set via the parameters installation height,
radius and scenario.
Scenario 9:
Small office, quiet workplace
This scenario offers maximum sensitivity. To avoid
undesired switching, this scenario should preferably
be used for small areas.
Scenario 8:
Large office, quiet workplace
Like scenario 9, but with slightly reduced sensitivity.
Also suitable for large areas.
Scenario 7:
Large office, large entrance area
Like scenario 8, but with further reduced sensitivity.
Scenario 6:
Hotel room, room with persons sleeping
This scenario also offers maximum sensitivity.
In addition, signal processing is optimised to reliably
detect the presence of persons sleeping.
Scenario 5:
Hotel room, room with persons sleeping
Like scenario 6, but with further reduced sensitivity.
Scenario 4:
Noisy workplace, light industry, hall
Vibrations can retrigger the sensor. This can lead to longer
stay-ON times in scenario 7-9. Scenario 4 works more
robustly.
Scenario 3:
Noisy workplace, light industry, hall
Like scenario 4, but with further reduced sensitivity.