- 14 -
- 15 -
5. Detection zone
Reliable presence detection depends largely on the number, quality and arrange-
ment of the lens elements. The IR Micro LiveLink - with its high-resolution sensor
system, including multi-segment pyro sensor - provides reliable, precision detec-
tion over 6 × 6 metres. The square detection zone provides the basis for creating
optimum configurations quickly and easily.
6. Technical specifications
presence
radial
tangential
presence
radial
tangential
Dimensions (Ø
×
D)
Ø 80
×
20.5 mm
Power consumption
3 mA / 2-DALI user,
12 - 22.5 V
, no SELV
Sensor technology
Passive infrared
Switching mode
LiveLink box
Detection zone
360° with 90° angle of aperture
(for ceiling lights)
(84 detection beams and 168 detection zones)
Reach
Square detection zone installed at a height of 3 m:
presence detection zone approx. 4 m × 4 m
Motion detector approx. 6 × 6 m
Time setting
From 1 min to 60 min via LiveLink box
Twilight setting
2 - 1000 lux (via LiveLink box)
IP rating
IP20
Temperature range
Ambient temperature -25°C to +55°C
7. Troubleshooting
Malfunction
Cause
Remedy
Light does not switch
ON
L
LiveLink box faulty
L
Lux setting too low
L
No motion being
detected
L
Replace LiveLink box
L
Slowly increase lux set-
ting until light switches
ON
L
Ensure unobstructed
sensor vision
L
Check detection zone
Light does not switch
OFF
L
Lux setting too high
L
Stay-ON time still effec-
tive
L
Interfering heat sources:
e.g. fan heater, open
doors and windows,
pets, light bulb / halogen
floodlight, moving ob-
jects
L
Reduce lux setting
L
Wait until stay-ON time
elapses; reduce stay-ON
time if necessary
L
Use stickers to mask out
stationary sources of
interference
Sensor switches OFF in
spite of persons being
present
L
Stay-ON time too short
L
Light-level threshold too
low
L
Increase stay-ON time
L
Change light threshold
Sensor does not switch
OFF quickly enough
L
Stay-ON time too long
L
Reduce stay-ON time
Sensor does not switch
ON quickly enough
when approached from
the front
L
Reach is reduced when
approached from the
front
L
Install additional sensors
L
Reduce distance be-
tween two sensors
Sensor does not switch
ON when persons are
present despite it being
dark
L
Lux setting too low
L
Sensor deactivated via
switch/button?
L
Semi-automatic mode?
L
Increase light-level
threshold
Sensor does not switch
ON selected basic
brightness in spite of it
being dark
L
Sensor in semi-automat-
ic mode
L
Lux setting too low
L
Switch sensor to fully
automatic mode
L
Increase light-level
threshold
Other faults
L
Sensor operating at the
limit of specific tempera-
ture ranges
L
See technical specifica-
tions