Operation – Without HBS-DC Installed
Operation – With HBS-DC Installed
Operation - HBS 300, HBS 200
The HBS 300 and HBS 200 operate by
turning lights ON automatically when
occupancy is detected and OFF when the
space is left vacant and the time delay
has elapsed. The sensor communicates
wirelessly to other wireless devices
programmed to the same group to turn
lights ON or OFF.
Light level function - HBS 300, HBS 200
The HBS sensor’s light level feature
keeps lighting OFF during daylight hours,
regardless of occupancy. A light level
delay-off function prevents the sensor
from responding to temporary changes
in ambient light level. If the ambient light
level is brighter than the set target value,
the sensor will wait for one minute before
turning lights OFF. If motion is detected
within this time, lights will remain ON.
After no motion is detected for one minute
and the light level has been greater than
the target value, the lights will turn OFF
and remain OFF until the daylight level
drops below the target set point and
motion is detected.
Operation - HBS 300, HBS 200
The HBS 300 and HBS 200 operate by
turning lights on and dimming lights
in response to scheduled or manual
overrides initiated from the Autani Energy
Manager.
Multiple HBS 300 and HBS 200 units may
be grouped together in the manager so
that occupancy transitions are shared by
the group, turning lights ON and OFF in
unison.
Light level function - HBS 300, HBS 200
The HBS sensor’s light level feature will
dim the fixture automatically if enabled in
the Autani Energy Manager.
The light harvesting feature allows each
light to maintain a constant level of
illumination directly under the fixture.
These settings must be configured in the
Autani Energy Manager if the HBS-DC
radio is installed.
Initial power up - HBS 300, HBS 200
Upon initial power up, the load will turn
ON for up to one minute. If no motion
is detected, the load will switch OFF. If
motion is detected and the target light
level setting is less than the daylight level,
the load will stay ON for the selected time
delay setting (per DIP switch setting). If
the daylight level at power up is greater
than the target light level setting, the load
will switch OFF regardless of occupancy.
Surge protection - HBS 300, HBS 200
The HBS sensors contains built in surge
protection. This feature will reset the
unit automatically after: power surges,
power outages, and power shortages.
Surge protection protects the sensor if it
is miswired as well. If miswired, shut off
power, correct the wiring, and the sensor
will then operate correctly.
Initial power up - HBS 300, HBS 200
Upon initial power up, the load will <check
with Bob Belz / Ibrahim for logic>
Surge protection - HBS 300, HBS 200
The HBS sensors contains built in surge
protection. This feature will reset the
unit automatically after: power surges,
power outages, and power shortages.
Surge protection protects the sensor if it
is miswired as well. If miswired, shut off
power, correct the wiring, and the sensor
will then operate correctly.
Light level - HBS 300, HBS 200
The light level feature allows lighting to
remain OFF during daylight, regardless of
occupancy. Daytime operation is at 200
footcandles (factory setting). Nighttime
operation is at .2 footcandles.
See Autani Manager documentation.
Light level teach mode - HBS 300, HBS 200
The light level teach mode reads the
ambient light level in the space and selects
this amount for the light level setting.
• Turn the light level setting to
• After 10 seconds, the value of the
ambient brightness is saved.
• This value is also available after a power
failure if the potentiometer is set to
teach mode at power up.
After setup and commissioning are
complete, adjust the light level settings to
fit the application needs.
Light level: .2 (night) to 200 (day) footcandles
Time
ON
1 2 3 4
Low
High
Low
High