- 14 -
- 15 -
Reach setting
(IR Quattro HD LiveLink)
Adjustment of the reach to
individual requirements
See table on page 5.
Potentiometer
d
The DUAL HF LiveLink sensor
has 2 special HF sensors that
detect movement from the
ceiling in both corridor direc-
tions. An app can be used to
set the reach electronically in
either direction at the same
time.
DUAL HF LiveLink - mounting height 2.8 m
Reach setting
(DUAL HF LiveLink)
Electrical installation / Automatic mode
The wiring leads selected for in-
stallation must comply with the
regulations laid down in VDE 0100
(see Safety Precautions on page
12). For the wiring of the presence
detector, the following applies:
Under section 6 of VDE 0100 520,
a multiple-core lead containing
both the mains voltage leads and
the control leads (e.g. NYM 5 x 1.5)
may be used for the wiring be-
tween sensor and LiveLink Box.
The lead between LiveLink Box
and sensor must be no longer
than 300 m (for 1.5 mm
2
). After
installing and switching on the
LiveLink Box, the sensor starts
to flash once a second during
the initialisation cycle.
IR Quattro HD LiveLink 40 s;
DUAL HF LiveLink 10 s.
DALI
.
.
.
.
L N
DA
DALI
DA
DA
DA
DA
L
N
L
N
S
DA
DA
LiveLink
BOX
EVG
LED
Sensor
DALI
Declaration of Conformity
This product complies with
- EMC Directive 2014/30/EU
- RoHS Directive 2011/65/EU
- WEEE Directive 2012/19/EU
Several sensors can be connect-
ed in a LiveLink system. In this
case, the maximum number of
DALI users must not be exceed-
ed (see Technical Specifications
on page 17)
Using several sensors
GB