2� General safety
precautions
!
Disconnect the power
supply before attempting
any work on the unit�
• During installation, the electric
power cable to be connected
must not be live. Therefore, switch
off the power first and use a volt-
age tester to make sure the wiring
is off-circuit.
• Installing the sensor involves work
on the mains power supply. This
work must therefore be carried
out correctly in accordance with
applicable national wiring regu-
lations and electrical operating
conditions. (e.g.:
DE:
VDE 0100,
AT:
OVE-EN 1,
CH:
SEV 1000)
• Only use genuine replacement parts.
• Repairs may only be made by
specialist workshops.
3� IR Quattro SLIM XS
Proper use
– Presence detector only suitable
for mounting on indoor ceilings.
– A device box with a depth of at
least 57 mm is required.
The sensor is connected to the
control unit via a DALI bus.
The sensor uses the DALI line for
communication and for supplying
power.
Package contents
(Fig� 3�1)
Product dimensions
(Fig� 3�2)
Product components
(Fig� 3�3)
A
Sensor module
B
Decorative trim panel
C
Sensor lens
D
Connecting terminal
4� Electrical connection
• Switch OFF power supply.
(Fig� 4�1)
Wiring up the sensor switch: under
section 6 of VDE 0100520, a mul-
ti-core lead containing both the mains
voltage leads as well as the control
leads (e.g. NYM 5 × 1.5 mm²) may be
used for the wiring between sensor
and DALI Application Controller.
The lead between DALI Application
Controller and sensor must be no
longer than 300 m (with 1.5 mm²).
After installing and switching ON, the
sensor flashes for 40 seconds.
Connecting the mains power supply
lead
(Fig� 4�1)
...
!
Note on parallel connection:
Several sensors can be connected
in a DALI-2 system. In this case,
the maximum number of DALI users
must not be exceeded
(
➜
"12� Technical specifications")
5� Mounting
• Check all components for
damage.
• Do not use the product if it is
damaged.
• Select an appropriate mounting
location, taking the reach and mo-
tion detection into consideration.
(Fig� 5�1 / 5�2)
Mounting procedure
• Switch off power supply
(Fig� 4�1)
• Detach decorative trim panel from
frame.
(Fig� 5�3)
• Fit mounting box Ø max. 68 mm
into the ceiling cut-out.
(Fig� 5�4)
• Connect to the mains power
supply.
(Fig� 5�5)
• Fit sensor module and screw into
place.
(Fig� 5�6)
• Fit decorative trim panel.
(Fig� 6�3)
• Switch ON power supply.
(Fig� 6�3)
• Make settings.
(
➜
"7� Function / operation")
6� Changing the detection
zone
Detection zone
(Fig� 6�1 / 6�2)
The film shroud provided is used
for minimising the detection zone
by a maximum of 40%.
7� Function / operation
Once you have connected the unit
and fitted the designer panel, you
are ready to put the system into
operation.
The sensor is put into operation
in accordance with the applicable
DALI-2 standard. All functions and
commands are available from DALI
standard IEC 62386 Part 101,
Part 103, Part 303 and Part 304. The
motion detection values and light
levels measured by the sensor can be
requested from the DALI Application
Controller. Automatic or time-based
cyclical transmission can also be
selected.
You will find detailed information
in the interface description on the
Internet at: DALI-2.steinel.de
LED function:
Red LED
Initialisation: LED flashes once every
2 seconds
Normal mode: LED stays OFF.
DALI identification: LED flashes once
a second.
8� Accessories
– Kaiser hollow-wall box
EAN 4007841000370
9� Care / maintenance
The product requires no mainte-
nance.
The detector lens may be cleaned
with a damp cloth if it gets dirty (do
not use cleaning agents).