12� Troubleshooting
Malfunction
Cause
Remedy
Light does not switch ON
n
No supply voltage
n
Lux setting too low
n
No motion being
detected
n
Check supply voltage
n
Slowly increase lux set-
ting until light switches
ON
n
Ensure unobstructed
sensor vision
n
Check detection zone
Light does not switch OFF
n
Lux setting too high
n
Stay-ON time still
effective
n
Interfering heat sources:
e.g. fan heater, open
doors and windows,
pets, light bulb / halo-
gen floodlight, moving
objects
n
Reduce lux setting
n
Wait until stay-ON time
elapses; reduce stay-
ON time if necessary
n
Use stickers to mask
out stationary sources
of interference
Sensor switches OFF
despite persons being
present
n
Stay-ON time too short
n
Light-level threshold too
low
n
Increase stay-ON time
n
Change twilight setting
Sensor does not switch
OFF quickly enough
n
Stay-ON time too long
n
Reduce stay-ON time
Sensor does not switch
ON quickly enough when
approached from the front
n
Reach is reduced when
approached from the
front
n
Install additional sensors
n
Reduce distance
between two sensors
Sensor does not switch
ON when persons are
present despite it being
dark
n
Lux setting too low
n
Sensor deactivated by
switch/button?
n
Semi-automatic mode?
n
Increase light-level
threshold
Switch not working
n
Switch deactivated?
n
Check DIP switch 3
setting
11� Technical specifications
Dimensions W × H × D
80 × 80 × 50 mm
Supply voltage
220-240 ~V / 50/60 HZ
Sensor system
Passive infrared (IR) / high-frequency
(HF)
Reach
IR max. 20 m (tangential) /
max. 4 m (radial) / HF max. 8 m
*
Angle of coverage
180°
Capacity, switching output 1
(COM1/COM2)
Relay 230 V
Resistive load max. 2000 W (cos φ = 1)
max. 1000 VA (cos φ = 0.5)
Electronic ballast (COM1)
Inrush current
max. 800 A / 200 μs
30 × (1 × 18 W), 25 × (2 × 18 W)
25 × (1 × 36 W), 15 × (2 × 36 W)
20 × (1 × 58 W), 10 × (2 × 58 W)
Note:
each electronic ballast has its own
particular inrush current.
A relay or contactor must be provided
upstream for higher switching capacities.
Output, switching output 2
presence (COM 2 only)
max. 230 W / 230 V
max. 1 A (cos φ = 1)
for HVAC (heating/ventilation /
air-conditioning)
Light-level setting
10-1000 lux, ∞ / daylight
Switching output 1
30 s - 30 min, pulse mode (approx. 2 s),
Time setting, IQ mode time (automatic
adjustment to usage profile)
Switching output 2
only COM2 for HVAC
Time setting 0 or 10 min switch-ON
delay.
5-15 min stay-ON time via (RC)
1 min - 2 h stay-ON time via Smart
Remote
Automatic room surveillance
Mounting height
1.1 m
Time setting
30 s - 30 min
IP rating
IP20
Temperature range
0°C to 40°C
*
At extreme angles, the reach of the
HF 180 is extensively determined by local
conditions.