- 26 -
- 27 -
Potentiometer
g
Potentiometer
h
Potentiometer
o
• Setting 1 min. – 2 hr.
• Turned fully clockwise: max
• Turned fully anti-clockwise: min
• Setting 0 sec. – 10 min.
• Turned fully clockwise:
Room surveillance
• Turned fully anticlockwise:
0 sec. (OFF)
Turning the potentiometer to the
"Surveillance" setting reduces the
sensitivity of the "Presence"
switching output.
The contact only closes on detect-
ing a pronounced movement, sig-
nalising with a high degree of cer-
tainty that persons are present.
The stay-ON time remains active.
The switch-ON delay is inactivated.
Switch-ON delay for switching output 2 HVAC
Reach adjustment
COM 2
Potentiometer
i
Provides basic illumination for the
selected stay-ON time when ambi-
ent light falls below the selected
light-level threshold that is set.
This can be dimmed to 10% of
maximum light intensity. As soon
as a person enters the scene, the
detector switches either to 100%
light intensity (constant-lighting
controller OFF) or adjusts to the
preselected light level (con-
stant-lighting controller ON). When
no movement is being detected,
the detector dims back to basic
light level after the stay-ON time
expires. This is switched OFF when
stay-ON time (1 min. – 30 min.) has
expired or the daylight component
is sufficient to exceed the selected
level of brightness. In the ON set-
ting, the detector switches basic
light level ON and OFF as soon as
the level of light falls below the
light-level threshold.
Basic light level (DIM version)
Stay-ON time for switching output 2 HVAC
The reach required (response
threshold) is infinitely variable.
<
US 360 / DualTech
at least 2 x 2 m - 6 x 6 m
presence
<
Single US / Dual US
at least 3 x 3 m - 10 x 3 m
in each direction
Turned fully anticlockwise =
minimum reach
Turned fully clockwise
(factory setting) = maximum reach
The master/slave configuration
permits detection of movement in
large-type rooms or spaces (load
connected = master, no load =
slave). The level of brightness pre-
vailing in the room is only evaluat-
ed at the master. The slaves report
movements detected to the mas-
ter. Lighting or HVAC is switched
ON and OFF by the master only.
Master/slave
A parallel-connected configuration
also permits the use of several
masters. In this case, each master
operates the lighting group in ac-
cordance with the level of bright-
ness it measures. Delay times and
light-level thresholds are selected
at each master as required. The
switched load is spread among the
individual masters. Presence is still
detected collectively by all detec-
tors. The presence output can be
picked off from any master.
Master/master
Remote control
Using the remote control (option-
al), functions can be conveniently
activated from the floor.
Note: The pulse mode cannot be
overridden by the remote control.
Switch pulse mode OFF manually.
Presence Control remote control
unit: EAN no: 4007841 559410
Parallel-connected configurations
Two detectors linked with an
external stairwell lighting tim-
er
Old building / building
modernisation
External light source activated by
button. No twilight mode, day
mode only.
Detector as stairwell lighting
timer
14.
1
14.
2
14.
3
14.
4
When using several detectors, they
must be connected to the same
phase!
As many as 10 sensors can be
connected in parallel.
DIM detector
14.
5
This external button cable is
not intended to serve as a
neutral conductor connec-
tion for loads (see page 6/7).
*
GB
Turned fully clockwise: The stay-
ON time is self-learning and ad-
justs dynamically to user behav-
iour.
The optimum time cycle is deter-
mined by means of a learning al-
gorithm.
The shortest time is 5 min., the
longest 20 min.
IQ-Modus
If the dial is set to (fully an-
ti-clockwise), the unit is in pulse
mode, i.e. the output is switched
ON for approx. 2 sec. (e.g. for stair-
well lighting timer). Afterwards,
the sensor does not react to move-
ment for approx. 8 sec. Day mode
is the only mode possible here be-
cause of dazzle by light from exter-
nal sources.
Pulse mode (except DIM)