- 24 -
- 25 -
DIP 6 / 7 / 8
Trigger mode
The trigger mode enables the user to choose which sensing technologies should be used
to initially turn the load on and which technologies are required to keep it on. The following
settings are possible:
DualTech COM1 / COM2 / DIM
Both:
Requires movement recognition by PIR and US
Either: Requires movement recognition by PIR or US
PIR:
Requires movement recognition by PIR
US:
Requires movement recognition by US
Inital occupancy:
Sensor technology used to turn the load on (PIR, US, Both, Either)
Maintain Occupancy:
Sensor technology used to keep the load on after initial occupancy (PIR, US, Both, Either)
The trigger mode is selected by DIP switches 6, 7 and 8.
Trigger mode
options
n
Initial presence
Maintain
presence:
DIP
6
DIP
7
DIP
8
Option 1
Both
Either
OFF
OFF
OFF
Option 2
Both
Both
OFF
OFF
ON
Option 3
PIR
Either
OFF
ON
OFF
Option 4
US
Either
OFF
ON
ON
Option 5 (factory setting)
Either
Either
ON
OFF
OFF
Option 6
US
US
ON
OFF
ON
Option 7
PIR
PIR
ON
ON
OFF
Option 8
Either
Both
ON
ON
ON
Functions – Settings by potentiometer
Examples of use
Light-level settings
Night-time mode
min
Corridors, foyers
1
Stairs, escalators, moving walkways
2
Washrooms, toilets, switchrooms, canteens
3
Sales floor, kindergartens, nursery school rooms,
sports halls
4
Work rooms: offices, conference and meeting
rooms, precision assembly activities, kitchens
5
Working areas requiring good light:
Laboratory, technical drawing, precision work
>=6
Daylight mode
max
Stay-ON time for switching
output 1
Setting 30 sec. – 30 min.
The chosen stay-ON time is in-
finitely variable from a minimum
of approx. 30 sec. to a maximum
of 30 min. Intrinsic light is cali-
brated after 3 min. When the
threshold is exceeded, the sensor
switches OFF after the stay-ON
time expires.
Time setting
The chosen response threshold
can be infinitely varied from ap-
prox. 10 – 1000 lux.
Control dial turned fully clockwise:
MAX daylight mode
Control dial turned fully
anti-clockwise: MIN night mode
Depending on the site of installa-
tion, the setting may need to be
corrected by 1-2 marks on the
scale.
Twilight setting
Potentiometer
e
Potentiometer
f
COM 1 + COM 2
Note: Depending on the site of installation, the setting may need to be corrected by 1 – 2 marks on the scale.
The light level is measured at the sensor.
GB
DIP 5
Provides a constant level of
brightness. Detector measures
the prevailing level of daylight
and activates sufficient artificial
light to achieve the required lev-
el of brightness. As daylight
changes, the switched-in artifi-
cial lighting component is ad-
justed accordingly. In addition to
the daylight component, artificial
light is also switched ON and OFF
in relation to whether or not per-
sons are present.
Constant light ON/OFF
DIM
on
1 2 3 4 5 6 7 8
TEST
MODE
MANUAL
ON / OFF
CONST.
OFF
NORMAL
MODE
AUTO
ON
CONST.
ON
TRIGGER MODE