Error Code Description

41

You have attempted to write to the Flash memory a second time which is not permitted. 

You may only write to the Flash memory one time after reprogramming. If you need to 

write to the Flash memory again, reprogram the heating system with ETS208 software or 

greater and then reconfigure. Reference Locations 98 and 99 (L098 and L099). 

42

If the check sum fails in the Flash copy of the settings or if the initial write to the Flash fails, 

Er42 is displayed. Reprogram the heating system or replace the processor control board.

43

An attempt to load a saved configuration by setting Location 98 (L098) to a value of 20, 

30, 40, or 50 has failed. Any changes to location values will need to be manually set. Press 

and release the “M” button to clear the error. Er43 is only applicable to processor control 

boards with a revision level of G or lower only. 

44

The check sum of the entire Flash is corrupt. Reprogram the heating system or replace the 

processor control board.

45

An attempt was made to load memory from an unsaved location in L098. Applicable to 

processor control boards with a revision level of H or higher only.

46

MA command or Pulse Width Modulation has timed out. No input has been received for 

30 minutes. If the MA command or Pulse Width Modulation are not being used, verify that 

Location 53 (L053) and/or Location 55 (L055) are set correctly for the application.

47

The Relay Driver Board is incompatible with the software version of the processor control 

board. Update the relay driver board. 

Cold Core The sensed temperature of the brick core is below 40 degrees. This may be an actual 

condition, a defective thermocouple, reversed polarity of thermocouple wiring coupled 

with a core temperature between 150°F (65°C) and 300°F (148°C), or a circuit board which 

is out of calibration can cause this. Verify that the core thermocouple wiring is connected 

properly and that the values in L090, L091 and L092 are correct for the application.  

Core Fail One of the core high limit switches may be open (also see error 38). 

PLC Fail 

The heater is configured for power line carrier; however, is not receiving a valid power line 

carrier communication signal. This will display as error 25 when using BACNet and PLC fail 

on the system display. 

LoAd CAP All controllable loads have been shed and Maximum Load Capacity is still exceeded. 

This is not necessarily an error but merely an indication of the current condition of the 

application. Example: If 4-20mA control is being used and comfort override or freeze 

protection brings on elements, this error code may be displayed.

T

herm

e

lecT

 h

ydronic

 

a

ppendix

| a.13

Summary of Contents for ThermElect Hydronic 9150

Page 1: ...OWNER S AND INSTALLER S MANUAL Models 9150 9180 ThermElect Elect Hydronic With Integrated SSR Control Applicable to Software Version 2 18 2 XX...

Page 2: ...ead all instructions prior to attempting to assemble install operate maintain or repair this product Upon unpacking of the system inspect all parts for damage prior to installation and start up This m...

Page 3: ...w describes these safety devices DEVICE NAME FUNCTION LOCATION ON SYSTEM Core Charging High Limit Switches Auto Reset These limit switches monitor the core and top temperatures If normal operating tem...

Page 4: ...04 Brick Loading 3 04 3 05 Heating Element Installation 3 05 3 06 Brick Core Temperature Sensor Installation 3 06 Line Voltage Electrical Connections 3 07 Low Voltage Electrical Connections Outdoor Te...

Page 5: ...another ducted heating system such as a heat pump SYSTEM USE DURING CONSTRUCTION PHASE Like most heating equipment manufacturers Steffes strongly recommends that Construction Heating Units be used ins...

Page 6: ...advanced operating modes updating software and troubleshooting OPERATING STATUS The four digit LED will display various operating information as described below Press and release the up arrow to view...

Page 7: ...t level which is determined by outdoor temperature utility peak conditions building automation system and or the heating requirements Sensors monitor the brick core temperature and communicate this in...

Page 8: ...ndle section The bottom part of the lifting handle must be installed with the hook facing down as shown in Figure 1B 5 Align the top and bottom parts of the lifting handle so the holes match up Use th...

Page 9: ...stem receives a signal from an external load control device such as a building load management system This external signal dictates the maximum amount of energy which can be consumed during a preset t...

Page 10: ...electrical panel HEATING ELEMENTS WITH CERAMIC INSULATORS Model Elements 9150 12 2 boxes of 6 9180 18 3 boxes of 6 shipped separately Installation 3 01 ThermElect Hydronic Installation SHIPPING AND PA...

Page 11: ...pped inside the electrical panel TOP AIR CHANNEL BLOCK shipped separately CERAMIC BRICK Model Brick LBS Pallets 9150 192 3 360 2 9180 288 5 040 3 96 brick per pallet shipped separately OUTDOOR TEMPERA...

Page 12: ...ystem must also be taken into consideration when selecting the installation location A level concrete floor is the designed installation surface however most well supported surfaces are acceptable If...

Page 13: ...2 Remove any and 1 trade size knockouts where the electrical panel mates to the units left side panel These openings may be knockouts or holes 3 Line up the electrical panel to these holes and fasten...

Page 14: ...ottom HEATING ELEMENT INSTALLATION Proper heating element installation is important to operation of the system Reference the Useful Tools section of the Heating Element Service and Repair Guide includ...

Page 15: ...through 1 2 knockout Connect the blue core blower wires to black and the blue wires Connect the two purple violet wires to the two purple wires BRICK CORE TEMPERATURE SENSOR INSTALLATION 1 Remove the...

Page 16: ...ing Diagrams Pages A 07 A 08 for more information on these connections 5 Mount and install step down transformer CONNECTION OF PRIMARY LOOP PUMP A 120 or 240V single phase pump can be used Connect the...

Page 17: ...an be hard wired to the system s OS and SC terminals default or it can be connected to the Power Line Carrier PLC transceiver When using BACnet control for outdoor temperature the outdoor sensor will...

Page 18: ...sure all connections including the valve inlet are clean and free from any foreign material Use pipe compound sparingly or tape on external threads only Mount the pressure relief valve in a vertical u...

Page 19: ...rom the system s heat exchanger The primary loop pump should be powered by ThermElect Hydronic control system as shown in Figure 11 If using other control method flow MUST continue for at least 30 sec...

Page 20: ...and or property It is the responsibility of the installer to provide protection against freezing PIPING SUPPORT Risk of equipment damage or personal injury DO NOT use the exchanger as support for pip...

Page 21: ...requires 30 PSI Pressure Relief Valve 60 PSIG requires 75 PSI Pressure Relief Valve Standard 125 PSIG requires 150 PSI Pressure Relief Valve Minimum Flow Rate Primary Loop 1 GPM per 10 000 BTU of req...

Page 22: ...PSI Pressure Relief Valve 60 PSIG requires 75 PSI Pressure Relief Valve Standard 125 PSIG requires 150 PSI Pressure Relief Valve Minimum Flow Rate Primary Loop 1 GPM per 10 000 BTU of required output...

Page 23: ...ThermElect Hydronic Appendix A 03 EXPLODED VIEW DIAGRAM 53 kW STORAGE MODULE The exploded view diagram is for reference only The ThermElect Hydronic storage module should not be disassembled...

Page 24: ...EXPLODED VIEW DIAGRAM 80 kW STORAGE MODULE The exploded view diagram is for reference only The ThermElect Hydronic storage module should not be disassembled Appendix A 04 ThermElect Hydronic...

Page 25: ...ock Kit Front 2009 and Older 1040220 1040219 11 Brick Each 96 Brick per Pallet 5903017 5903017 12 Cast Block Bottom 1056501 1056501 13 Limit Switch EGO 575Deg 1013026 1013026 14 Insulation Blanket 2 4...

Page 26: ...12 Inlet Pipe Cover 5948526 DWG Ref Description Item 13 Outlet Pipe Cover Left Half 5948525 14 Outlet Pipe Cover Right Half 5948527 15 Left Side Exchanger Panel 5948524 16 Base Panel Rear Painted 594...

Page 27: ...ThermElect Hydronic Appendix A 07 TYPICAL SYSTEM LINE VOLTAGE WIRING DIAGRAM NOTE Use copper or aluminum conductors rated for 75o C or higher for field connection of this device...

Page 28: ...ing 9180 Shown NOTE The R and C positions in the low voltage terminal strip may be used as a source of 24 VAC for powering external low voltage devices 60 VA maximum WARNING HAZARDOUS VOLTAGE Risk of...

Page 29: ...il the targeted brick core charge level is displayed Using the charge control override or the building management system initiate a full charge Once initiated the heating system will target 100 percen...

Page 30: ...s C1_x Specialty Timer 1 Charge Mode Specialty Applications Only C2_x Specialty Timer 2 Charge Mode Specialty Applications Only HUxx Heat Usage Indicates the amount of input being dissipated by the sy...

Page 31: ...verify proper calibration of the circuit board Approximate ohm readings are 60 F 1552 ohms 70 F 1199 ohms 80 F 941 ohms Max 190 F Min 0 09 Auxiliary analog input is out of normal operating range Curre...

Page 32: ...r the Energy Management Controller may be unresponsive Check the jumper configuration on the Energy Management Controller and make sure J1 is ON and J2 is OFF Verify that the value in L053 is correct...

Page 33: ...n received for 30 minutes If the MA command or Pulse Width Modulation are not being used verify that Location 53 L053 and or Location 55 L055 are set correctly for the application 47 The Relay Driver...

Page 34: ......

Page 35: ......

Page 36: ...F THIS DOCUMENT STEFFES SHALL NOT BE LIABLE FOR ANY LOSSES CLAIMS DAMAGES OR LIABILITY RELATING TO LOST PROFITS OR OTHER CONSEQUENTIAL INCIDENTAL EXEMPLARY PUNITIVE OR INDIRECT DAMAGES IN CONNECTION W...

Reviews: