7
745.089 | 11.30
EN
3.3
Establishing the electrical connections
Danger
Risk of death by electrocution! Make sure that the following conditions are satisfied
when performing the work described in this section:
• All cables leading to the controller must be disconnected from the power supply and
it must be ensured that they cannot be unintentionally reconnected during installa-
tion.
• Each connection terminal must only be connected to a single conductor.
• The protective earth conductors (PE) from the mains cable and pump and valve
cables must be connected to the
protective earth conductor terminal block
.
• All cables must be laid so that persons cannot stand on them or trip over them.
• The cables must satisfy the requirements listed in the
Technical data
section.
• The local power supply must match the specifications on the type plate of the con-
troller.
• The power supply cable is to be connected to the mains power as follows:
– using a plug connected to a wall mains socket
or
– via an isolating mechanism allowing complete isolation in the case of permanent
wiring.
• The power supply cable must be laid in conformance to all applicable legal guide-
lines and regulations of the local electricity supplier.
Notice
Danger of damage and malfunction.
• Connect only components that do not overload the controller inputs and outputs;
more information is provided on the type plate and in the
Technical data
section.
• Speed control must be deactivated at output
R1
when an external relay is con-
nected.
Notes
• Lay the sensor cables at least 100 mm away from any power supply cables.
• Use shielded sensor cables when inductive sources are present, e.g. high-voltage
lines, radio transmitters, microwave devices.
Summary of Contents for TF B001
Page 23: ...23 745 089 11 30 EN Notes...
Page 24: ...24 745 089 11 30 EN 745089...