ATTENTION!
Danger of damage to the inverter or derating!
–
The mounting location must satisfy the following conditions:
–
The mounting location and immediate environment are permanently fixed, vertical, flat,
non-inflammable and not subject to constant vibration.
–
The permissible ambient conditions are conformed to; see Technical data
p. 133 et seqq.
–
The following free spaces must be present around the inverter:
Above/below: at least 200 mm
At the sides/in front: at least 60 mm
–
Do not install the inverter in areas where animals are kept.
–
Observe the connection ratings specified on the type plate.
–
The DC cables must not be connected to an earth potential (DC inputs and AC output are not
galvanically isolated).
ATTENTION!
When transmitting data over a public network:
–
Transmitting data over a public network can incur additional costs.
–
Data transmitted over a public network is not protected from unauthorised access by third-
parties.
Note
–
Avoid exposing the inverter to direct sunlight.
–
The display must be readable on the installed device.