I N S T A L L A T I O N
Installation steps :
1. Posi oning & moun ng of
SR (S, C, SX or CX)
steam ramp to the ven la on duct wall
by using metal screw
2. Install the steam hose or rigid steam pipe between the IER steam humidifier and the
steam ramp.
Note: when using rigid stem pipe (stainless steel or copper) it is a good prac ce to
connect in between the steam ramp, IER humidifier and pipe by using a small length of
steam hose for ease of installa on and service.
Allow for a slope of 2° minimum.
3. Secure all connexion with hose clamps
4. For SRC or SRCX install a condensate hose in between steam ramp and IER humidifier.
Provide a condensate trap of 8in [200mm] minimum as shown on above figure.
Allow for a slope of 2° minimum
5. Secure all connexion with hose clamps
Remote Space Blower
Condensate trap 8in
[200mm] minimum
Steam pipe/hose
slope 2° minimum
Condensate line
slope 2° minimum
Can be returned to humidifier or directed to an open drain.
Open drain
Ver cal run 6in
[150mm] minimum
Figure 18 – Steam & condensate line for Remote SB
Installation steps :
Please refer to space blower IOM