I N S T A L L A T I O N
Installation – step 1
IER Positioning & Mounting
General guidelines for positioning
IER
electric steam humidifier should be posi oned so that:
Length of the steam line (or hose) is as short as possible,
In case steam hose is used, the bend radius of 12in (300mm) is ensured
Humidifier is easily accessible for service
CAUTION. Risk of malfunc on due to vibra on. Do Not mount IER
electric steam
humidifier directly on ven la on duct
.
CAUTION. Risk of flooding.
Ensure that the local where
IER
electric steam
humidifier will be installed is equipped
with floor drain.
In case of no floor drain is available; installa on of a water leak detector is required
in order to prevent any flooding in case of abnormal opera on or service.
IER
electric steam humidifier should be installed in a well-ven lated and dry environment.
If local is subject to below freezing point temperature, ac va on of ant freezing func on of
the
IER
electric steam humidifier is required.
For outdoor installa on please contact your steamOvap representa ve to order and install
special outdoor op onal enclosure for
IER
.
IER
maximum ambient condi ons:
Temperature: 41°F to 113°F [+5 to +45°C]
Rela ve Humidity: 90%RH max (non condensing)
Ingress Protec on for
IER
standard enclosure: IP20
12