background image

3. Instructions for Installation

11/10

Pub. No. 573-B

- 6 -

Instructions for Installation and Use

heater, fill rock cavity with igneous stones provided with 
heater and fasten metal protective grill on top of heater. (See 
gen. info concerning washing and placing of stones.)

3.3.2. 3-phase Heater Wiring and Hookup (SMS-100-3,
SMS-125-3, SMS-145-3)

Refer to table 2 for proper wire size and amperage. See 

figures 2–6 for required clearances. Use copper wire from 
breaker to wall-mounted power unit. Supply cable must have 
4 wires including insulated neutral and separate ground.

Use 90 °C copper wire from power unit to room light. Also 

use 90 °C copper wire from power unit to sauna heater 
(within seal tight flex conduit), and connect to junction box 
under heater at back, with 90 °C connector.

If connection to heater will be made at a later time, bring 

flex into sauna room 4–6” from floor, and leave 3’ of flex for 
hookup (can be cut to right length later). Before testing 
heater, fill rock cavity with igneous stones provided with 
heater and fasten metal protective grill on top of heater. (See 
gen. info concerning washing and placing of stones.)

3.4. After Installation

3.4.1. Testing of Sauna Heater 
1. After sauna heater has been properly wired, according to 

appropriate wiring diagram and local codes, turn sauna 

breaker on in the main breaker panel. (Note: Electrician 
must label “Sauna” breaker.)

2. Turn thermostatic (heat) control to on position (this is 

located either on your heater or on your remote wall 
control. If you have a wall control, the indicator light will 
come on to show that the sauna is heating). Set timer to 10 
or 15 minutes.

3. Within 5 minutes, you should be able to feel heat from 

heater elements when holding your hand over heater.

4. If the sauna does not heat, refer to troubleshooting 

information.

5. It is normal for smoke to appear during the first heating, as 

protective element coating needs to burn off. Turn sauna 
on for 1 hour before using the first time, to eliminate 
smoking.

3.4.2. Troubleshooting

A. If the sauna heater does not operate after initial 

installation and wiring:

1. Make sure that a neutral wire has been included. This is 

necessary for all heaters except model with built-in 
control).

2. Check circuit breaker in contactor to be sure that it has not 

been shorted out.

3. Make sure that the current from the control unit to the 

heater has been switched on.

4. Check that the desired temperature programmed in the 

control panel is higher than the temperature of the sauna.

B. If the sauna has been in operation, but the heater 

ceases to operate:

1. Check breaker to make sure it is on.

2. Check that there is on time left in the control panel.

3. Check overheat limiter reset button in heater (reset is 

under the heater) to see if it has been released.

4. Call your electrician or service person for further help.

NOTE: A GROUND FAULT INTERRUPTER (GFI) should not 
be installed in and does not belong in a sauna. If used, the 
breaker will trip, and damage could result.

C. If the sauna heater operates, but the sauna room does 

not come up to sauna temperature (149–176 ºF)

1. You must allow at least 30 minutes for sauna heat-up time.

2. Is the sauna thermometer located 6” from ceiling, and is it 

above or close to the sauna heater? (This is proper 
location for sauna temperature reading.) Thermometer 
readings vary with room heights and location. Eg.180 ºF 
above sauna heater = 165 on opposite wall = 140 on upper 
bench level = 120 on lower bench level = 100 at floor level.

Table 1

Model

Heater kW

Minimum

Ceiling

Height

Minimum

Floor Area

in Square

Feet

Maximum

Floor Area

in Square

Feet

Sauna Room

Minimum

Cubic Feet

Sauna Room

Maximum

Cubic Feet

Minimum

Spacing From

Adjacent 

Surfaces

SMS-100

SMS-100-3

SMS-125

SMS-125-3

SMS-145

SMS-145-3

10 kW

12.5 kW

15 kW

6'-6"

6'-6"

6'-6"

60

78

97

94

114

146

390

500

630

600

750

1000

5 inches

6 inches

6 inches

Model

SMS-100-3

SMS-125-3

SMS-145-3

Watts

9,800

12,300

14,400

Amps

27.3

34.1

40.0

Voltage

208

208

208

Phase

3

3

3

Breaker to Power Unit

1@35A - #8 AWG copper 90°C 

1@45A - #6 AWG copper 90°C 

1@50A - #6 AWG copper 90°C 

Power Unit to Heater

#8 AWG copper 90°C 

#6 AWG copper 90°C 

#6 AWG copper 90°C 

Control

S170-3

S170-3

S170-3

S170-1

S170-1

S170-1

SMS-100

SMS-125

SMS-145

10,000

12,600

14,800

41.7

52.5

61.7

240

240

240

1

1

1

Breaker to Load Center

1@60A - #4 AWG copper 90°C

1@70A - #4 AWG copper 90°C

1@80A - #3 AWG copper 90°C

Load Center to Power Unit

2@35A - #8 AWG copper 90°C

2@35A - #8 AWG copper 90°C

2@40A - #8 AWG copper 90°C

Power Unit to Heater

#8 AWG copper 90°C

#8 AWG copper 90°C

#8 AWG copper 90°C

Table 2

Note: neutral wire required

Summary of Contents for SMS-100

Page 1: ...of the Sauna Stones The sauna stone for an electric heater should be 2 4 in diameter The heater stones should be solid blocks of stone specially intended for use in the heater Neither light porous cer...

Page 2: ...on the heated stones to reach a suitable level of humidity in the sauna The humidity of the air in the sauna room is controlled by the amount of water thrown on the stones A correct level of humidity...

Page 3: ...need to exit the room C Unawareness of impending hazard D Fetal damage in pregnant women E Physical inability to exit the room F Unconsciousness WARNING the use of alcohol drugs or medication is capab...

Page 4: ...warning texts on the cover of the junction box can also be read without difficulty after the installation SMS heaters have not been approved to be installed in a recess in the wall or floor 3 2 Insta...

Page 5: ...f this manual 3 3 1 Single Phase Heater Wiring and Hookup SMS 100 SMS 125 SMS 145 Refer to table 2 for proper wire size and amperage See figures 2 6 for required clearances Use copper wire from breake...

Page 6: ...with built in control 2 Check circuit breaker in contactor to be sure that it has not been shorted out 3 Make sure that the current from the control unit to the heater has been switched on 4 Check tha...

Page 7: ...verheating Limiter Each heater is equipped with an overheating limiter which is a safety device If an abnormal heating condition should occur the heater will automatically shut off and it will not com...

Page 8: ...manufacturer s agent after the defective parts are returned to Steamist The replacement of parts under warranty does not extend the warranty period beyond the original one year period In addition Ste...

Reviews: