background image

Ø 3mm

ELECTRICAL  INSTALLATION

Screw Driver

TURN OFF SUPPLY BEFORE   WORKING ON 
ANY ELECTRICAL CONNECTION

Vs

Loop 
Load

+

-

+

-

10

9

8

7

SEM1603TC

5

4

OUTPUT
2 Wire (4-20) mA 
Max cable length 1000 meters
Use twisted pair cable > 30 meters

SUPPLY (Vs)  = (11 to 30) VDC

MAX  LOAD

Ohms  = (Vs - 11) / 0.021

INPUT CONNECTION
For cable lengths < 3 meters shielded or twisted pair is not required.
For cable lengths > 3 meters and < 30 meters shielded or twisted pair is required.
Cable lengths > 30 meters are not recommended.
Inputs of all three wires must be equal length (resistance).

m

V

+

+

-

-

8

7

7

8

T/C

MECHANICAL INSTALLATION

SEM1603  Enclosure

Style

DIN 43880 (1 module width)

Material       

Polyamide 6.6 self extinguishing

Terminals

Screw terminal

Cable

2.5 mm Max

Color

Gray

Ø 3  mm

90 mm

MOUNTING

Screw driver

EN50022 DIN RAIL

56.4 mm

17.5 mm

1
2

11 12

10

9

8

7

4

5

6

1

2

3

To fit or release module

Insert screw driver into

slot and lever latch

away from body

1

2

+ 70 °C Max

- 20 °C Min

Ø 3

  m

m

1

2

SEM1603TC_User_GuideUSA_5-08

Reviews: